OLNEY, IL —
OSHA Inspection: ESCALADE SPORTS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ESCALADE SPORTS INC. in 4594 EAST RADIO TOWER LANE, OLNEY, IL 62450 (NAICS 339920). OSHA activity number 340566926.
Where did this inspection happen?
- Establishment
- ESCALADE SPORTS INC.
- Site address
- 4594 EAST RADIO TOWER LANE
- City
- OLNEY
- State
- IL
- ZIP
- 62450
- Mailing
- 4594 EAST RADIO TOWER LANE, OLNEY, IL 62450
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339920
- Employees
- 35
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $2295.00 · Current $2295.00
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: East Section of Production Area, at the Hayssen #8 machine, the flexible electrical cord for the Powermax 110 volt pedestal fan, was missing its electrical grounding pin in the plug.
Recent events (2)
- — I (S) $2295
- — Z (S) $2295
1910.334 A02 I
- Issued
- Abate by
- Penalty
- Initial $2295.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): a) In the north section of the Plastics Production Area, at the BMM #5 electrical panel, a black flexible 110 volt power cord outer insulation had pulled away from the plug, exposing the inner wiring. b) In the north section of the Plastics Production Area, near the BMM #5 electrical panel, an orange 110 extension cord outer insulation was apart exposing the inner wiring.
Recent events (2)
- — I (S) $0
- — Z (S) $2295
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $2295.00 · Current $2295.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: East Section of Production Area, at the Hayssen machine controls #019619, on the 110 volt 2 switch electrical box, the right side switch had been removed, leaving its opening in the faceplate.
Recent events (2)
- — I (S) $2295
- — Z (S) $2295
More inspections in this industry (NAICS 339920)
MINNEAPOLIS, MN—2026-07-06 00:00:00
111526 - MINNESOTA IMPRINTS LLC
OWATONNA, MN—2026-07-01 00:00:00
111509 - POWERBLOCK INC
EAST STROUDSBURG, PA—2026-04-29 00:00:00
RIDDELL ALL AMERICAN SPORTS INC
BUENA VISTA, GA—2026-04-29 00:00:00
ARMAGEDDON GEAR
GRANTS PASS, OR—2026-04-14 00:00:00
317743828 - PLAYCRAFT SYSTEMS LLC
More inspections in IL
FRANKFORT, IL—2026-07-17 00:00:00
QUANTUM TECHNICAL SERVICES INC.
ROCK ISLAND, IL—2026-07-17 00:00:00
AUGUSTANA COLLEGE
WASHINGTON, IL—2026-07-17 00:00:00
SUNRUN INSTALLATION SERVICES, INC.
FOREST PARK, IL—2026-07-17 00:00:00
CONSERVATION OF SCULPTURE & OBJECTS STUDIO, INC.
BLUE ISLAND, IL—2026-07-17 00:00:00
PROFLOW PUMPING SOLUTIONS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340566926.