Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EXPERA SPECIALTY SOLUTIONS, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of EXPERA SPECIALTY SOLUTIONS, LLC in 24 PORTLAND ST, OLD TOWN, ME 04468 (NAICS 322110). OSHA activity number 340635473.

Watch Expera Specialty Solutions, LLC — free Get an email when a new federal OSHA severe-injury report for Expera Specialty Solutions, LLC is published. One employer, no account, unsubscribe in one click.
Site address
24 PORTLAND ST
City
OLD TOWN
State
ME
ZIP
04468
Mailing
24 PORTLAND ST, OLD TOWN, ME 04468
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322110
Employees
158
Ownership type
A

4 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 3 instances 20 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $3500.00 Reduced

Hazardous substances W103

29 CFR 1910.22(a)(1): Places of employment were not kept clean and orderly and in a sanitary condition:   Truck Dump #2 conveyer room, Silo Building shaker room, and North Wood Room - Accumulations of combustible dust, a Class II Group G combustible dust, generated during the moving and sizing of wood chips, settled on floors, equipment, structural members, and electrical equipment in these work areas.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $5000

1910.303 F02

Serious Gravity 1 1 instance 50 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $2100.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  Panel 8-01-082 - The 24 breakers in this panel were not labeled as to their purpose.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3000

1910.157 E02

Other-than-serious 4 instances 150 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  Throughout the facility - Portable fire extinguishers have not been visually inspected at least monthly.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E03

Other-than-serious 4 instances 158 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  Facility wide - Portable fire extinguishers have not been subjected to an annual maintenance check.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View EXPERA SPECIALTY SOLUTIONS, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340635473.