Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ENTERPRISE WIRE PRODUCTS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ENTERPRISE WIRE PRODUCTS, INC. in 5300 PORT BOULEVARD S., ATLANTA, GA 30349 (NAICS 332618). OSHA activity number 341041960.

Watch Enterprise Wire Products, INC. — free Get an email when a new federal OSHA severe-injury report for Enterprise Wire Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
5300 PORT BOULEVARD S.
City
ATLANTA
State
GA
ZIP
30349
Mailing
P.O. BOX 849, RED OAK, GA 30272
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332618
Employees
21
Ownership type
A

6 citations on file for this inspection.

1910.157 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $1360.00 · Current $816.00 Reduced
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  (a) In the Sheet Metal and Tubing area, on the north wall, a portable fire extinguisher was not mounted, located and identified so it was readily accessible without subjecting the employees to injuries.
Recent events (2)
  • — I (S) $816
  • — Z (S) $1360

1910.303 G01

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $1360.00 · Current $816.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a) In the Sheet Metal and Tubing area, on the north wall, sufficient access and clearance was not provided and maintained for an electrical service panel, exposing employees to electrical and trip hazards.
Recent events (2)
  • — I (S) $816
  • — Z (S) $1360

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $1700.00 · Current $1020.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  (a) In the Sheet Metal and Tubing area, on the north wall, unused openings in an electrical service panel were not effectively closed, exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1020
  • — Z (S) $1700

1910.147 C01

Other-than-serious 1 instance 19 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  (a) In the production areas, the employer did not establish a lockout/tag out program consisting of energy control procedures, employee training, and periodic inspections. Equipment covered under this OSHA standard included, but was not limited to, metal benders and resistance welders.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 L04 III

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:  (a) Throughout the facility, Komatsu forklift operators were not evaluated to ensure the operators had the knowledge and skill necessary to operate the forklift safely at least every three years.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 H03 IV

Other-than-serious 1 instance 21 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(h)(3)(iv): Employees had not been provided with Globally Harmonized System (GHS) 2012 training with respect to the labeling, pictograms, and safety data sheets, including the order of information, and how employees could obtain and use the appropriate hazard information:  (a) Throughout the facility, the employer did not provide training to employees on the new hazard communication standard Globally Harmonized System (GHS) as a result, employees were not familiar with the new hazard communication standard. Employees were exposed to hazardous chemicals in the workplace, such as but limited to, acetylene, compressed oxygen, propane, carbon dioxide gas, lubricants and powder coatings.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ENTERPRISE WIRE PRODUCTS, INC.'s full OSHA safety record →