1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: CHAMPION COOLER CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CHAMPION COOLER CORPORATION in 1724 S. SCULLIN AVE., DENISON, TX 75020 (NAICS 333415). OSHA activity number 341237626.

Watch Champion Cooler Corporation — free Get an email when a new federal OSHA severe-injury report for Champion Cooler Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1724 S. SCULLIN AVE.
City
DENISON
State
TX
ZIP
75020
Mailing
1724 S. SCULLIN AVE., DENISON, TX 75020
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333415
Employees
185
Ownership type
A

4 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $2700.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks.  In the machining area, employees operated a Summit lathe with the chuck and cutting tool not guarded exposing the employees to the being struck-by and or caught-in the rotating parts and flying chips.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.303 E01 II

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $1620.00 Reduced
29 CFR 1910.303(e)(1)(ii): Electrical equipment was used when the markings giving voltage, current, wattage, or other ratings as necessary were missing.  In the press room, electrical equipment (panels) were in use and were not marked with necessary ratings such as voltage or current exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $1620
  • — Z (S) $2700

1910.303 G01 II

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $1620.00 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  In the large press area, product was stored in front of electrical equipment exposing employees to fire hazards.
Recent events (2)
  • — I (S) $1620
  • — Z (S) $2700

1910.305 G01 IV A

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  In the large press area, the employer used a flexible cord in lieu of permanent fixed wiring to power a water cooler exposing employees to electrical shock and fire hazards.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

View CHAMPION COOLER CORPORATION's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341237626.