Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: JOINT BASE ELMENDORF-RICHARDSON

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of JOINT BASE ELMENDORF-RICHARDSON in 3RD MAINTENANCE GROUP AEROSPACE GROUND EQUIPMENT FLIGHT, JBER, AK 99506 (NAICS 488119). OSHA activity number 342008182.

Watch Joint Base Elmendorf-Richardson — free Get an email when a new federal OSHA severe-injury report for Joint Base Elmendorf-Richardson is published. One employer, no account, unsubscribe in one click.
Site address
3RD MAINTENANCE GROUP AEROSPACE GROUND EQUIPMENT FLIGHT
City
JBER
State
AK
ZIP
99506
Mailing
10441 KUTER AVE, JBER, AK 99506
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488119
Employees
30
Ownership type
D

1 citation on file for this inspection.

1910.159 C10

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained.   Building 8574, Communications Room; on or about 03 January 2017 and times prior thereto, a storage cabinet wall was constructed eight inches below the sprinkler head. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
  • — Z (S) $0

View JOINT BASE ELMENDORF-RICHARDSON's full OSHA safety record →

AK, INC