Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: ROCHESTER GAS & ELECTRIC CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ROCHESTER GAS & ELECTRIC CORP. in 1101 BEACH AVE, ROCHESTER, NY 14612 (NAICS 221112). OSHA activity number 342360229.

Watch Rochester GAS & Electric Corp. — free Get an email when a new federal OSHA severe-injury report for Rochester GAS & Electric Corp. is published. One employer, no account, unsubscribe in one click.
Site address
1101 BEACH AVE
City
ROCHESTER
State
NY
ZIP
14612
Mailing
89 EAST AVENUE, ROCHESTER, NY 14649
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
850
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12675.00 · Current $7500.00 Reduced
OSH ACT of 1970 Section (5)(a)(1):  The employer did not furnish to each of his employees employment and a place of employment which were free from recognized hazards that were causing or were likely to cause death or serious physical harm to it's employees:    a)   On or about May 30, 2017 at Substation #7, Beach Avenue, Rochester, NY as part of the inspection and testing of the circuit breaker for capacitors 1R7402 and 1R7412 (an atypical configuration for this type of equipment within the employer's system), the employer did not provide adequate training as to the configuration of the electric feed to capacitors 1R7402 and 1R7412, so as to assist employees in recognizing the hazards of entering an adjacent cabinet without first arranging for the de-energizing of the adjacent cabinet.
Recent events (3)
  • — J (S) $7500
  • — C (S) $12675
  • — Z (S) $12675

1910.269 C04 II B

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(c)(4)(ii)(B): The employee could not be expected to recognize and avoid the hazards involved in the job and a more extensive briefing was not held;   a) On or about 05/30/18 at Substation #7, Beach Avenue, Rochester, NY; the inspection and testing of circuit breakers for capacitors 1R7402 and 1R7412, located in metal cabinets and connected to underground energized conductors  (an atypical configuration for this type of equipment within the system), did not necessitate the employer to require a more extensive job briefing (tail board) to include the hazards associated this type of circuit breaker configuration and the hazards of associated with accessing the north side of the cabinets, i.e. the presence of energized conductors (11kV) and the use of protective measures such as but not limited to, voltage testing, installation of protective covers, additional personal protective equipment, confirmation of the line diagram review.     ABATEMENT DOCUMENTATION REQUIRED
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.269 M03 II

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12675.00 · Current $0.00 Reduced
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be denenergized were open.    a) On or about 05/30/18 at Substation #7, Beach Avenue, Rochester, NY, as part of the switching orders for the inspection and testing of the circuit breaker for capacitors 1R7402 and 1R7412, (an atypical configuration for this type of equipment within the system), employer did not include the isolation and the denergizing of the known source of electrical energy, Line 555 which supplied power to the circuit breaker disconnects.      ABATEMENT DOCUMENTATION REQUIRED
Recent events (3)
  • — J (S) $0
  • — C (S) $12675
  • — Z (S) $12675

View ROCHESTER GAS & ELECTRIC CORP.'s full OSHA safety record →

GENERA PR