CELINA, OH —
OSHA Inspection: LAKE CONTRACTING COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LAKE CONTRACTING COMPANY in 1 VISIONS PARKWAY, CELINA, OH 45822 (NAICS 238220). OSHA activity number 342468360.
Where did this inspection happen?
- Establishment
- LAKE CONTRACTING COMPANY
- Site address
- 1 VISIONS PARKWAY
- City
- CELINA
- State
- OH
- ZIP
- 45822
- Mailing
- 225 S. BUCKEYE STREET, CELINA, OH 45822
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 11
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $5070.00 · Current $3570.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) On July 10, 2016, at Vision Awardcraft in Celina, Ohio: The employer did not ensure that employees were provided with adequate training on electrical safety-related work practices such as, but not limited to, the use of personal protective equipment and lock out tag out to protect against electrical hazards while working on or near energized or potentially energized electrical parts. Employees were exposed to 480 volts electrical hazards while performing troubleshooting and repair work on an Allied heating and cooling unit.
Recent events (2)
- — I (S) $3570
- — Z (S) $5070
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $5070.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) On July 10, 2017, the employer did not ensure that employees troubleshooting a 480 volt Allied heating and cooling unit were protected from electrical shock and arc flash hazards. Employees were not wearing personal protective equipment such as, but not limited to, hand protection while performing electrical work.
Recent events (2)
- — I (S) $0
- — Z (S) $5070
1910.333 A01
- Issued
- Abate by
- Penalty
- Initial $5070.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a) On July 10, 2016, at Vision Awardcraft in Celina, Ohio: the employer did not ensure an employee was protected from electrical hazards in that the Allied heating and cooling unit was not deenergized and locked out before employees accessed it for repair. The employee was exposed to a 480 volt electrical hazard while working near live parts while performing troubleshooting and repair work.
Recent events (2)
- — I (S) $0
- — Z (S) $5070
1910.333 B02 III A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $3570.00
General-duty citation text
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to deenergize circuits and equipment on which work was to be performed: On July 10, 2016, at Vision Awardcraft in Celina, Ohio: the employer did not assure that a lock and tag was applied to the disconnecting means for the Allied heating and cooling unit when an employee removed a relay. Employees were exposed to 480 volt electrical hazards when performing work on the unit.
Recent events (2)
- — I (S) $3570
- — Z (S) $0
More inspections in this industry (NAICS 238220)
SAN MARCOS, TX—2026-07-16 00:00:00
CASA MECHANICAL SERVICES, LTD.
RIO RANCHO, NM—2026-07-15 00:00:00
PROFESSIONAL STUCCO & SERVICE INC.
BROOKLYN, NY—2026-07-15 00:00:00
DILIGENT AC LLC
PARKVILLE, MD—2026-07-15 00:00:00
AMERICAN AUTOMATIC SPRINKLER COMPANY, INC.
SACRAMENTO, CA—2026-07-15 00:00:00
J.R. PIERCE PLUMBING CO., INC. OF SACRAMENTO
More inspections in OH
WELLINGTON, OH—2026-07-16 00:00:00
WHIRLAWAY CORPORATION
WAUSEON, OH—2026-07-16 00:00:00
WATSON WELL DRILLING INC.
SEVEN HILLS, OH—2026-07-15 00:00:00
STONEY ACRES BUILDERS LLC
SEVEN HILLS, OH—2026-07-15 00:00:00
GRB ENTERPRISES LLC
CHILLICOTHE, OH—2026-07-15 00:00:00
KENWORTH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342468360.