Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MHI HOTEL SERVICES, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of MHI HOTEL SERVICES, LLC in 1700 SMITH STREET, HOUSTON, TX 77002 (NAICS 721110). OSHA activity number 342771763.

Watch MHI Hotel Services, LLC — free Get an email when a new federal OSHA severe-injury report for MHI Hotel Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1700 SMITH STREET
City
HOUSTON
State
TX
ZIP
77002
Mailing
1700 SMITH STREET, HOUSTON, TX 77002
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
120
Ownership type
A

4 citations on file for this inspection.

1910.332 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9239.00 · Current $6929.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:     a)  At the facility, where employees working near energized electrical equipment when assisting and supervising the work being performed by contractors were not trained and familiar with the safety-related work practices required by 1910.331 through 1910.335.
Recent events (2)
  • — I (S) $6929
  • — Z (S) $9239

1910.333 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9239.00 · Current $6929.00 Reduced
1910.333(a)(1):   Live parts to which an employee may be exposed were not deenergized before the employee works on or near them, unless the employer could demonstrate that deenergizing introduces additional or increased hazards or was infeasible due to equipment design or operational limitations:       a)  At the facility, on or about November 10, 2017, where the electricity running to the Square D Power Style, 4 section switchgear was not deenergized prior to employees working near them.
Recent events (2)
  • — I (S) $6929
  • — Z (S) $9239

1910.333 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9239.00 · Current $6929.00 Reduced
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives:     a)  At the facility, where written procedures for using safety related work practices on the Square D Power Style, 4 section switchgear were not maintained.
Recent events (2)
  • — I (S) $6929
  • — Z (S) $9239

1910.335 A01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9239.00 · Current $6930.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:      a)  At the facility, on or about November 10, 2017, where the Chief Engineer was not provided with and did not use electrical protective equipment that would protect his body and face from arc flashes.
Recent events (2)
  • — I (S) $6930
  • — Z (S) $9239

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342771763.