NEW YORK, NY —
OSHA Inspection: JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL in 10 COLUMBUS CIRCLE 6TH FLOOR, NEW YORK, NY 10023 (NAICS 711110). OSHA activity number 343507307.
Where did this inspection happen?
- Establishment
- JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL
- Site address
- 10 COLUMBUS CIRCLE 6TH FLOOR
- City
- NEW YORK
- State
- NY
- ZIP
- 10023
- Mailing
- 3 COLUMBUS CIRCLE, NEW YORK, NY 10019
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 711110
- Employees
- 500
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G01 I B
- Issued
- Penalty
- Initial $13260.00 · Current $13260.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater. Location: 10 Columbus Circle, New York, NY, 6th Floor; In the North Mechanical Room On or about 10/2/2018, a) The working space in front of the 480 Volt dry type transformer was minimized to approximately 9 inches due to stored equipment.
Recent events (2)
- — I (O) $13260
- — Z (S) $13260
1910.303 G01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage. Location: 10 Columbus Circle, New York, NY; 6th Floor; In the North Mechanical Room On or about 10/2/2018, a) The work spaces in front of a 480 Volt dry type transformer and a 120 Volt switchgear were used for storage of food service equipment.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections at JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL
NEW YORK, NY—2011-07-29 00:00:00
JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL
View JAZZ AT LINCOLN CENTER - FREDERICK P. ROSE HALL's full OSHA safety record →
More inspections in this industry (NAICS 711110)
LANGLEY, WA—2026-06-11
WA317991612 - ISLAND SHAKESPEARE FESTIVAL
TACOMA, WA—2026-04-23
WA317990927 - DREAMGIRLS OF TACOMA LLC
BOSTON, MA—2026-02-26
LIVE NATION ENTERTAINMENT, INC.
SAN FRANCISCO, CA—2026-02-09
AMERICAN CONSERVATORY THEATER
SANTA FE, NM—2026-02-04
NEW MEXICO DEPARTMENT OF CULTURAL AFFAIRS
More inspections in NY
MAYVILLE, NY—2026-07-16
MAYVILLE VILLAGE DPW
NEW HYDE PARK, NY—2026-07-16
NORTH HEMPSTEAD TN MICHAEL J TULLY PARK
CONESUS, NY—2026-07-16
CONESUS TN HIGHWAY DEPT
COMSTOCK, NY—2026-07-15
NYSDOCCS WASHINGTON CORRECTIONAL FACILITY
BALDWINSVILLE, NY—2026-07-15
LYSANDER TOWN HIGHWAY DEPARTMENT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343507307.