Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: GENERAL DYNAMICS NASSCO

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GENERAL DYNAMICS NASSCO in M/V USS MIGUEL KEITH 2798 E. HARBOR DR., SAN DIEGO, CA 92113 (NAICS 336611). OSHA activity number 343631859.

Watch General Dynamics Nassco — free Get an email when a new federal OSHA severe-injury report for General Dynamics Nassco is published. One employer, no account, unsubscribe in one click.
Site address
M/V USS MIGUEL KEITH 2798 E. HARBOR DR.
City
SAN DIEGO
State
CA
ZIP
92113
Mailing
PO BOX 85278, SAN DIEGO, CA 92186
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
3200
Ownership type
A

5 citations on file for this inspection.

1915.89 C01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $14586.00
29 CFR 1915.89(c)(1): The employer did not ensure that, before any authorized employee performed servicing when energization, startup, or the release of hazardous energy could occur, that all energy sources were identified and isolated, and the machinery, equipment, or system was rendered inoperative:    USS Miguel Keith, STBD Casing 1-34-1: On November 28, 2018, employees were performing a continuity check on a panel containing energized components. Prior to starting the work, all energy sources were not identified and isolated. An employee contacted two different phases of the line side concurrently with a set of alligator clips, causing an arc flash. The employee was exposed to electrical shock and/or burn hazards from 480 volts.
Recent events (2)
  • — I (S) $14586
  • — Z (S) $13260

1915.181 B

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $0.00 Reduced
29 CFR 1915.181(b): Before an employee was permitted to work on an electrical circuit, except when the circuit must remain energized for testing and adjusting, the circuit was not de-energized and checked at the point at which the work was done to ensure that it was actually de-energized:    USS Miguel Keith, STBD Casing 1-34-1: On November 28, 2018, employees were performing a continuity check on a panel containing energized components. An employee contacted two different phases of the line side concurrently with a set of alligator clips, causing an arc flash. The employee was exposed to electrical shock and/or burn hazards from 480 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13260

1915.152 A

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $14586.00
29 CFR 1915.152(a): The employer did not provide or ensure each affected employee with the appropriate personal protective equipment (PPE) for the eyes, face, head, extremities, torso, and respiratory system, including protective clothing, protective barriers, personal fall protection equipment, and life saving equipment, meeting the applicable provisions of Subpart I, wherever employees were exposed to work activity hazards that required the use of PPE.     USS Miguel Keith, STBD Casing 1-34-1: On November 28, 2018, an employee was performing a continuity check on a panel with energized components while wearing a hard hat, safety glasses, hearing protection, and safety shoes. Electrical-related personal protective equipment for the face and neck was not utilized. The employee was exposed to electrical shock and/or burn hazards from 480 volts.
Recent events (2)
  • — I (S) $14586
  • — Z (S) $13260

1915.152 B

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $0.00 Reduced
29 CFR 1915.152(b): The employer did not assess its work activity to determine whether there were hazards present, which necessitate the employee's use of personal protective equipment:    USS Miguel Keith, STBD Casing 1-34-1: On November 28, 2018, an employee was performing a continuity check on a panel with energized components within inches of the work. The employer's hazard assessment for working on high voltage electrical equipment did not include protection for adjacent exposed energized parts that could be accidentally contacted.  The employee was exposed to electrical shock and/or burn hazards from 480 volts when he inadvertently made contact with energized parts of the panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13260

1915.157 C

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $0.00 Reduced
29 CFR 1915.157(c): The employer did not ensure that affected employees wore protective electrical insulating gloves and sleeves or other electrical protective equipment when exposed to the risk of electrical shock:    USS Miguel Keith, STBD Casing 1-34-1: On November 28, 2018, an employee was performing a continuity check on a panel with energized components while wearing a hard hat, safety glasses, hearing protection, and safety shoes. Electrical-rated personal protective equipment for the hand and/or body was not utilized. The employee was exposed to electrical shock and/or burn hazards to the hands and body from 480 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13260

View GENERAL DYNAMICS NASSCO's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343631859.