Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WESTERN REFINING COMPANY, L.P.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WESTERN REFINING COMPANY, L.P. in 6501 TROWBRIDGE DRIVE, EL PASO, TX 79905 (NAICS 324110). OSHA activity number 343784831.

Watch Western Refining Company, L.P. — free Get an email when a new federal OSHA severe-injury report for Western Refining Company, L.P. is published. One employer, no account, unsubscribe in one click.
Site address
6501 TROWBRIDGE DRIVE
City
EL PASO
State
TX
ZIP
79905
Mailing
212 N. CLARK STREET, EL PASO, TX 79905
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
409
Ownership type
A

6 citations on file for this inspection.

1910.119 F01

Deleted Serious Gravity 5 2 instances 16 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $0.00 Reduced
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and shall address at least the following elements.  On or about February 12, 2019 at the El Paso Western Refining Facility, the employer did not develop and implement a written operating procedure for:  a) Taking spent catalyst samples.  b) Safely conducting activities with tanks listed as Intercat Main Catalyst Feed Tank (F-353), Olefin Additive tank (F-354) and Co-Promotor Additive Tank (F-355).
Recent events (2)
  • — I (S) $0
  • — Z (S) $9472

1910.119 J02

Other-than-serious 2 instances 16 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $13260.00
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment.     On or about February 12, 2019 at the El Paso Western Refining Facility, the employer failed to ensure that written procedures for testing interlocks were established and implemented such as but not limited to:      a) Interlock INT 301-5 Spent Cat Slide Valve Low Differential Shutdown (P&ID 300-011-10025-817 Rev.12).    b) Interlock INT 301-2 Low Air Flow to Regenerator Heater H-3000 (P&ID 300-011-10025-811 Rev.11).
Recent events (2)
  • — I (O) $13260
  • — Z (S) $13260

1910.119 J04 I

Other-than-serious 8 instances 16 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $13260.00
29 CFR 1910.119(j)(4)(i): The employer did not perform inspections and tests on process equipment.       On or about February 12,2019 at the El Paso Western Refining Facility, the employer did not perform inspections and testing on the following process equipment:    a) Intercat Main Catalyst Feed Tank (F-353).      b) Pressure Safety Valve PVS- W16233 located on the top of the Intercat Main Catalyst Feed Tank (F-353).      c) Interlocks:        1. Interlock INT 301-5 Spent Cat Slide Valve Low Differential Shutdown (P&ID 300-011-10025-817 Rev.12).        2. Interlock INT 301-2 Low Air Flow to Regenerator Heater H-3000  (P&ID 300-011-10025-811 Rev.11).    d) Controls and Indicators:           1. Level Control LC-258 (P&ID 300-011-10025-817 Rev.12).        2. Differential Pressure Indication PDI-225 (P&ID 300-011-10025-817 Rev.12).        3. Temperature Control TC-178 (P&ID 300-011-10025-811 Rev.11).        4. Fire Eyes BA-300A (P&ID 300-011-10025-811 Rev.11).
Recent events (2)
  • — I (O) $13260
  • — Z (S) $13260

1910.119 D03 I B

Other-than-serious 3 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate.     On or about February 12, 2019 at El Paso Western Refining Facility, the employer did not ensure that piping and instrument diagrams (P&IDs) were accurate.  The P&IDs were not updated and accurate for the following:      a) P&ID 300-011-10025-810 Rev. 15, did not include the Fresh Cat Loader, Diesel Compressor, Drier Skids, Boiler House, FCC Loop, and Intercat Additive.      b) P&ID 130-011-10025-830 Rev. 13, did not include the Chemical Injection Point.      c) P&ID 300-011-10025-V01 Rev. 02, did not include line connecting tanks F-354 and F-355 to the process.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 H03 IV B

Other-than-serious 3 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(h)(3)(iv)(B): Certification information on a tag or label was not attached to the storage compartment for the respirator and kept with the respirator or included in inspection reports stored as paper or electronic files:    On or about February 12, 2019 at the El Paso Western Refining Facility, the employer did not ensure that inspection reports for emergency Self-Contained Breathing Apparatus (SCBAs) were attached by paper or electronic files for the following:      a) Station #5 (1011737).    b) Station #6 (1011745).    c) Station #7 (1011757).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.146 C02

Other-than-serious 4 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.146(c)(2): If the workplace contains permit spaces, the employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces.     On or about February 12, 2019 at the El Paso Western Refining Facility, the employer did not inform employees by posting danger signs or by any other equally effective means at locations containing permit spaces for the following:    a) LCO Stripper (F-1301) skirt in the Fluidized Catalyst Cracking Unit (FCCU).    b) Off Gas Amine Column (F-1311) skirt in the FCCU.     c) Second stage reactor (F-8906) skirt in the Catalyst Gasoline Hydrotreater (CGHT).    d) Vessel F-8140 skirt in the Alkylation unit.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0