Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KANZA COOPERATIVE ASSOCIATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of KANZA COOPERATIVE ASSOCIATION in 109 MAIN ST., IUKA, KS 67066 (NAICS 424910). OSHA activity number 343975629.

Watch Kanza Cooperative Association — free Get an email when a new federal OSHA severe-injury report for Kanza Cooperative Association is published. One employer, no account, unsubscribe in one click.
Site address
109 MAIN ST.
City
IUKA
State
KS
ZIP
67066
Mailing
P.O. BOX 175, IUKA, KS 67066
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424910
Employees
21
Ownership type
A

3 citations on file for this inspection.

1910.110 B06 VII

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5114.00 · Current $3580.00 Reduced
29 CFR 1910.110(b)(6)(vii): The minimum separation between liquefied petroleum gas containers and flammable liquid tanks shall be 20 feet:    Employees exposed to explosive hazards.  Employees engaged in propane forklift tank exchange activities were exposed to explosive hazards in that the stored liquefied petroleum gas containers and flammable liquid tanks were not separated by 20 feet.
Recent events (2)
  • — I (S) $3579.8
  • — Z (S) $5114

1910.110 F02 II

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $5115.00 · Current $3580.00 Reduced
29 CFR 1910.110(f)(2)(ii): Liquefied petroleum gas container(s) stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people:    Employees exposed to chemical and explosive hazards.  Employees engaged in propane forklift tank exchange activities were exposed to chemical and explosive hazards in that the stored liquefied petroleum gas containers stored inside were located near an exit intended for the safe exit of people.
Recent events (2)
  • — I (S) $3579.8
  • — Z (S) $5115

1910.303 F02

Other-than-serious 3 instances 21 exposed
Issued
Abate by
Penalty
Initial $5114.00 · Current $3580.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Employees were exposed to electrical shock hazards. Employees engaged in warehouse and shop operations were exposed to electrical shock hazards in that the employer did not legibly mark electrical branch panels in the foam fill room to indicate its purpose in the following areas:    a) Electrical branch circuit in the chemical building panel B    b) Electrical branch circuit in the chemical building panel A    c) Electrical branch circuit in the main building shop area
Recent events (2)
  • — I (O) $3579.8
  • — Z (S) $5114

View KANZA COOPERATIVE ASSOCIATION's full OSHA safety record →