OSHA Inspection: HUDSON COMPANY OF TENNESSEE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HUDSON COMPANY OF TENNESSEE in 1731 MONTGOMERY HWY, BIRMINGHAM, AL 35244 (NAICS 236220). OSHA activity number 344292248.

Watch Hudson Company OF Tennessee — free Get an email when a new federal OSHA severe-injury report for Hudson Company OF Tennessee is published. One employer, no account, unsubscribe in one click.
Site address
1731 MONTGOMERY HWY
City
BIRMINGHAM
State
AL
ZIP
35244
Mailing
PO BOX 429, HENAGAR, AL 35978
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
85
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $6564.00 · Current $3938.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  (a)  On or about 9/06/19 - 1731 Montgomery Highway, Hoover, AL, a subcontractor was allowed to operate a Rigid Power Drive that was plugged into a receptacle housed in a metal box that was not mounted.
Recent events (2)
  • — I (S) $3938.4
  • — Z (S) $6564

1926.404 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:  (a)  On or about 9/06/19 - 1731 Montgomery Highway, Hoover, AL, a subcontractor was allowed to operate a Rigid Power Drive that was plugged into a receptacle that did not have a GFCI receptacle.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 A02 II I

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(I): Protection was not provided to avoid damage to flexible cords and cables used for temporary wiring which passed through doorways or other pinch points:  (a)  On or about 9/06/19 - 1731 Montgomery Highway,  Hoover, AL, a subcontractor was allowed to operate a Rigid Power Drive plugged into an extension cord that was pinched under a metal door and connected to a receptacle inside the building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View HUDSON COMPANY OF TENNESSEE's full OSHA safety record →