BOURBON, MO —
OSHA Inspection: TOWN AND COUNTRY SUPERMARKETS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TOWN AND COUNTRY SUPERMARKETS in 150 W. PINE STREET, BOURBON, MO 65441 (NAICS 445110). OSHA activity number 344607627.
Where did this inspection happen?
- Establishment
- TOWN AND COUNTRY SUPERMARKETS
- Site address
- 150 W. PINE STREET
- City
- BOURBON
- State
- MO
- ZIP
- 65441
- Mailing
- 150 W. PINE STREET, BOURBON, MO 65441
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 15
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C01
- Issued
- Abate by
- Penalty
- Initial $8675.00 · Current $6073.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisted of energy control procedures, employee training and periodic inspections to ensure that before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source, and rendered inoperative: A lockout/tagout program, including written procedures for specific machines or operations, such as when working on electrical equipment, training of employees who perform lockout/tagout, providing lockout devices and locks, and periodic inspections, was not established and implemented for employees performing work requiring lockout, such as, but not limited to, working on electrical equipment, such as changing and installing circuit breakers in live electrical panels. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $6072.5
- — Z (S) $8675
1910.303 F01
- Issued
- Abate by
- Penalty
- Initial $5205.00 · Current $3644.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: In the motor control rooms, all circuit breakers, electrical panel boxes, and disconnecting equipment was not labeled. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $3643.5
- — Z (S) $5205
1910.303 G01 V
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(v): Illumination was not provided for all working spaces about service equipment, swtichboards, panelboards, and motor control centers installed indoors: a. At the circuit breaker panel next to the produce prep area, there was no lighting over the panel. Employees used circuit breakers to turn on/off store lighting. b. In the motor control rooms, there was no lighting, including for changing out circuit breakers in electrical panel boxes not able to be de-energized. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 F01 VIII
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(f)(1)(viii): The employer shall ensure that all circuit breakers used as switches are labelled "SWD". At the circuit breaker panel next to the produce prep area, circuit breaker(s) used to turn on/off store lighting was not rated as SWD. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $8675.00 · Current $6073.00 Reduced
General-duty citation text
CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a. In the motor control rooms, live electrical equipment such as but not limited to, live contacts and connections in electrical panel boxes and contactor boxes were not covered. b. In the produce area of the store, wiring from a light fixture was exposed. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $6072.5
- — Z (S) $8675
1910.304 E01 I
- Issued
- Abate by
- Penalty
- Initial $8675.00 · Current $6073.00 Reduced
General-duty citation text
29 CFR 1910.304(e)(1)(i): Means was not provided to disconnect all conductors in a building or other structure from the service-entrance conductors: In motor control room #1, where service entry entered the building, a main disconnect was not available to disconnect power to the circuit breaker panel immediately downstream from the service entry. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $6072.5
- — Z (S) $8675
1910.333 A02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved: In motor control room #1, where there was no main disconnect work was required to be done on a circuit breaker panel with live contacts/connections. Safe work practices were not provided for electrical work as stated in paragraph (c). Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 C02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(c)(2): The employer did not ensure that qualified persons were capable of working safely on energized circuits and were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools: In motor control room #1, where there was no main disconnect work was required to be done on a circuit breaker panel with live contacts/connections. Safe work practices were not provided for electrical work such as the employer providing personal protective equipment (e.g. insulated gloves), insulated tools, and shields if needed. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 445110)
MOORESVILLE, NC—2026-07-08
161504 - FOOD LION, LLC
GREENVILLE, SC—2026-07-08
77565 - HARRIS TEETER
OGDEN, UT—2026-07-08
BIG DEAL OUTLET
MARYSVILLE, WA—2026-07-07
WA317991952 - SAFEWAY INC
ELLICOTT CITY, MD—2026-07-07
SPROUTS FARMERS MARKET
More inspections in MO
KANSAS CITY, MO—2026-07-09
NIAGARA BOTTLING
MONETT, MO—2026-07-09
MONETT METALS INC.
PARKVILLE, MO—2026-07-08
SKY-TECH ROOFING, LLC.
SPRINGFIELD, MO—2026-07-07
D & C CONSTRUCTION, LLC.
JOPLIN, MO—2026-07-07
SERVICE RECYCLING - NORTH PLANT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344607627.