TAUNTON, MA —
OSHA Inspection: NORTH EAST REFRIGERATED TERMINALS, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of NORTH EAST REFRIGERATED TERMINALS, INC. in 81 INGELL STREET, TAUNTON, MA 02780 (NAICS 493110). OSHA activity number 345169262.
Where did this inspection happen?
- Establishment
- NORTH EAST REFRIGERATED TERMINALS, INC.
- Site address
- 81 INGELL STREET
- City
- TAUNTON
- State
- MA
- ZIP
- 02780
- Mailing
- 81 INGELL STREET, TAUNTON, MA 02780
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 18
- Ownership type
- A
Citations
7 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $3735.00 Reduced
General-duty citation text
29 CFR OSH ACT of 1970 Section (5)(a)(1):Section 5(a)(1) of the Occupational Safety and Health Act: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a potential catastrophic release of ammonia gas or liquid resulting in irritation, pulmonary edema, skin burns and frostbite from the deficient design and lack of maintenance of the ammonia refrigeration facility and equipment: (a) Main King Valve - The hand operated Main King valve located above the receiver was not accessible for operation from the floor exposing employees to the risk of exposure to ammonia gas or liquid; (b) Machinery Room - The machinery room had several holes and openings where cables, piping, and wiring ran through that were not sealed to prevent the transfer of liquid, moisture, air, or vapor exposing employees to the risk of exposure to ammonia gas or liquid; (c) Machinery Room - The machinery room did not contain an audio and visual alarm to warn that access to the room is restricted to authorized and emergency personnel.
Recent events (2)
- — I (S) $3735
- — Z (S) $9557
1910.36 D01
- Issued
- Abate by
- Penalty
- Initial $5461.00 · Current $2135.00 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: (a) Maintenance Shop Near Engine Room: Exit door 13 was locked with a chain and padlock from the outside preventing employees from opening from the inside.
Recent events (2)
- — I (S) $2135
- — Z (S) $5461
1910.37 B04
- Issued
- Abate by
- Penalty
- Initial $5461.00 · Current $2135.00 Reduced
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: Throughout the facility where the direction of travel was not clear signs were not posted to indicate the nearest exit from the building. This exposed employees to hazards associated with anhydrous ammonia, fire, and cold.
Recent events (2)
- — I (S) $2135
- — Z (S) $5461
1910.37 B05
- Issued
- Abate by
- Penalty
- Initial $5461.00 · Current $2135.00 Reduced
General-duty citation text
29 CFR 1910.37(b)(5):Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet): (a) Throughout the facility and freezers doors that were not an exit were not marked as not an exit.
Recent events (2)
- — I (S) $2135
- — Z (S) $5461
1910.38 D
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $3735.00 Reduced
General-duty citation text
29 CFR 1910.38(d):The employer did not have and maintain an employee alarm system with a distinctive signal for each purpose that complied with the requirements in � 1910.165. Facility: The alarm system for reporting the release of anhydrous ammonia was the same system for a fire. They were not separate and distinct from one another.
Recent events (2)
- — I (S) $3735
- — Z (S) $9557
1910.38 E
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.38(e):The employer did not designate and train employees to assist in a safe and orderly evacuation of other employees: Facility: Throughout the facility the employer did not train employees in the safe and orderly evacuation of employees in the case of emergency to include the release of anhydrous ammonia.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.38 F01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.38(f)(1):The employer did not review the emergency action plan with each employee covered by the plan when the plan was developed or when the employee was initially assigned to a job: Facility: The employer failed to review and train employees on the emergency action plan upon plan development and assignment of employees.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 493110)
PORTSMOUTH, VA—2026-07-15 00:00:00
DACS INC
WEST CHESTER, OH—2026-07-14 00:00:00
CRESCENT PARK CORPORATION
WEYMOUTH, MA—2026-07-14 00:00:00
SPEEDX
MEMPHIS, TN—2026-07-13 00:00:00
STG LOGISTICS, INC.
MOCKSVILLE, NC—2026-07-13 00:00:00
161537 - KONTOOR BRANDS, INC.
More inspections in MA
WESTFORD, MA—2026-07-17 00:00:00
M&M CONSTRUCTION SERVICES CORP
ATTLEBORO, MA—2026-07-16 00:00:00
R M PACELLA INC
LYNN, MA—2026-07-16 00:00:00
A.M.B. IRON LLC
NEWTON, MA—2026-07-16 00:00:00
A&S CARPENTRY, INC.
BELLINGHAM, MA—2026-07-16 00:00:00
BELLINGHAM DEPARTMENT OF PUBLIC WORKS