CHIPPEWA FALLS, WI —
OSHA Inspection: NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION in 6350 163RD STREET WISSOTA FALLS HYDRO PLANT, CHIPPEWA FALLS, WI 54729 (NAICS 221111). OSHA activity number 345690242.
Where did this inspection happen?
- Site address
- 6350 163RD STREET WISSOTA FALLS HYDRO PLANT
- City
- CHIPPEWA FALLS
- State
- WI
- ZIP
- 54729
- Mailing
- 1414 WEST HAMILTON AVENUE, EAU CLAIRE, WI 54701
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221111
- Employees
- 38
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.1408 A01
- Issued
- Abate by
- Penalty
- Initial $14502.00 · Current $11602.00 Reduced
General-duty citation text
29 CFR 1926.1408(a)(1): The employer failed to identify the work zone by either demarcating the boundaries and prohibiting the operator from operating the equipment past those boundaries, or defining the work zone as the area 360 degrees around the equipment and up to the equipment's maximum working radius: (a) Near Wissota Falls hydro plant; On or before December 8, 2021, the work zone was not identified or defined before a National Crane brand, swing seat boom truck crane, model NBT-36, was used to unload barges, spud holders, and spuds for winter storage. An employee was injured when the load line contacted an overhead transmission line on December 8, 2021 and passed away as a result of those injuries.
Recent events (2)
- — I (S) $11601.6
- — Z (S) $14502
1926.1408 A02
- Issued
- Abate by
- Penalty
- Initial $14502.00 · Current $11602.00 Reduced
General-duty citation text
29 CFR 1926.1408(a)(2): The employer did not determine if any part of the equipment, load line or load (including rigging and lifting accessories), if operated up to the equipment's maximum working radius in the work zone, could get closer than 20 feet to a power line: (a) Near Wissota Falls hydro plant; On or before December 8, 2021, no determination was made before a National Crane brand, swing seat boom truck crane, model NBT-36, was used to unload barges, spud holders, and spuds for winter storage. An employee was injured when the load line contacted an overhead transmission line on December 8, 2021 and passed away as a result of those injuries.
Recent events (2)
- — I (S) $11601.6
- — Z (S) $14502
1926.1408 B01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.1408(b)(1): The employer did not conduct a planning meeting with the operator and the other workers who will be in the area of the equipment or load to review the location of the power line(s), and the steps that will be implemented to prevent encroachment/electrocution: (a) Near Wissota Falls hydro plant; On or before December 8, 2021, the location of power lines and the steps to prevent encroachment/electrocution were not reviewed with workers before a National Crane brand, swing seat boom truck crane, model NBT-36, was used to unload barges, spud holders, and spuds for winter storage near an overhead 69kV power transmission line. An employee was injured when the load line contacted an overhead transmission line on December 8, 2021 and passed away as a result of those injuries.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
LA POINTE, WI—2023-07-17 00:00:00
NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
MENOMONIE, WI—2023-05-11 00:00:00
NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
EAU CLAIRE, WI—2022-08-09 00:00:00
NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
MENOMONIE, WI—2022-05-26 00:00:00
NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION
View NORTHERN STATES POWER COMPANY, A WISCONSIN CORPORATION's full OSHA safety record →
More inspections in this industry (NAICS 221111)
UMATILLA, OR—2026-05-29 00:00:00
DEPT. OF DEFENSE - USACE
UMATILLA, OR—2026-05-29 00:00:00
DEPT. OF DEFENSE - USACE
EVERETT, WA—2026-05-20 00:00:00
WA317991327 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
CRAIG, AK—2026-05-12 00:00:00
ALASKA POWER & TELEPHONE COMPANY
SULTAN, WA—2026-04-15 00:00:00
WA317990791 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
More inspections in WI
GREEN BAY, WI—2026-07-17 00:00:00
PTS CONTRACTORS, INC.
WAUSAU, WI—2026-07-16 00:00:00