OBERLIN, OH —
OSHA Inspection: FABRITECH SOLUTIONS, LLC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of FABRITECH SOLUTIONS, LLC in 46701 U.S. 20, OBERLIN, OH 44074 (NAICS 332323). OSHA activity number 346798119.
Where did this inspection happen?
- Establishment
- FABRITECH SOLUTIONS, LLC
- Site address
- 46701 U.S. 20
- City
- OBERLIN
- State
- OH
- ZIP
- 44074
- Mailing
- 46701 U.S. 20, OBERLIN, OH 44074
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332323
- Employees
- 6
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B01
- Issued
- Abate by
- Penalty
- Initial $4688.00 · Current $2813.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 27, 2023, the employer did not ensure that employees were protected from electrical hazards in that current-carrying parts of a 3-phase 50A Hubbell plug end device, used to power the Roll-In Saw (model DT1340; s/n 08004DT) bandsaw, were not safeguarded. An employee sustained fatal electrical injuries after contacting live parts of the 480-volt plug connection. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $2813
- — Z (S) $4688
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $3349.00 · Current $2009.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about April 3, 2023, the employer did not ensure that a 3-phase 50A Hubbell plug end device was installed and used according to listing instructions in that the plug device was not used with a hard service round type cord. The plug was installed and used with unsupported Metal-Clad Cable (Type MC) for power to the 480V Roll-In Saw (model DT1340; s/n 08004DT) bandsaw, exposing employees to electrical shock hazards. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $2009
- — Z (S) $3349
1910.303 G01
- Issued
- Abate by
- Penalty
- Initial $2679.00 · Current $1608.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 27, 2023, the working space and access to the 480-volt electrical equipment located on the back side of the Roll-In Saw (model DT1340; s/n 08004DT) bandsaw was not maintained. The east wall and tools, such as a ladder and grinder, stored within the space hindered an employee's ability to access or perform work on the machine's electrical equipment. b. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 27, 2023, the employer did not ensure that access to the main electrical panelboard, located on the east wall, and controls power sources in the welding/fabrication area, was maintained. Access to the electrical panelboard was obstructed by welding equipment, hindering an employee's ability to access the equipment in the event of an emergency or perform work on the panels as needed. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $1608
- — Z (S) $2679
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $4688.00 · Current $2813.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1):Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 27, 2023, the employer did not ensure that employees who are exposed to electrical hazards when installing electrical wiring and components were trained in electrical safety-related work practices as required by 1910.331-1910.335. Employees performing work on or near circuits of the 480V Roll-In Saw (model DT1340; s/n 08004DT) bandsaw which were, or may have been energized, were not trained in the skills necessary to distinguish exposed live parts from other parts of electrical equipment. b. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 20, 2023, the employer did not ensure that employees who are exposed to electrical hazards when performing electrical tests were trained in electrical safety-related work practices as required by 1910.331-1910.335. Employees performing work on or near circuits of the 480V shop-made hydraulic press which were, or may have been energized, were not trained on electrical shock, arc flash hazards, and protective equipment to protect against electrical hazards. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $2813
- — Z (S) $4688
1910.333 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(a):Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 20, 2023, the employer did not develop and implement electrical safety related work practices which cover employees exposed to live electrical conductors while performing electrical work. Employees responsible for performing electrical tests in the 480V electrical enclosure for a shop-made hydraulic press which were, were exposed to hazards in that electrical safe work practices were not employed to prevent electrical shock and/or arc flash/blast injuries. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $4688.00 · Current $2813.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed. a. Fabritech Solutions, LLC - Oberlin, Ohio: On or about June 20, 2023, the employer did not ensure workers who performed electrical tests in a 480-volt electrical control panel for the shop-made hydraulic press, were provided with and used electrical protective equipment. An employee testing for voltage was exposed to electrical shock and arc flash hazards while performing the electrical test. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
- — I (S) $2813
- — Z (S) $4688
More inspections in this industry (NAICS 332323)
PACOIMA, CA—2026-07-14 00:00:00
AMERICAN IRONWORKS MANUFACTURING, INC.
PATERSON, NJ—2026-07-08 00:00:00
TOWN GATE CO. INC.
HUDSON, NC—2026-07-01 00:00:00
161479 - TRINITY MANUFACTURING GROUP, LLC
ARCHBOLD, OH—2026-06-30 00:00:00
BIL-JAX INC.
IRVINE, CA—2026-06-29 00:00:00
MISSION VIEJO ORNAMENTAL IRON, INC.
More inspections in OH
DAYTON, OH—2026-07-17 00:00:00