JOINT BASE PEARL HBR HICKAM, HI —
OSHA Inspection: U.S. NAVY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. NAVY in 850 TICONDEROGA STREET, JOINT BASE PEARL HBR HICKAM, HI 96860 (NAICS 928110). OSHA activity number 346887318.
Where did this inspection happen?
- Establishment
- U.S. NAVY
- Site address
- 850 TICONDEROGA STREET
- City
- JOINT BASE PEARL HBR HICKAM
- State
- HI
- ZIP
- 96860
- Mailing
- 850 TICONDEROGA ST STE 110, JOINT BASE PEARL HBR HICKAM, HI 96860
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 850
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.27 B01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.27(b)(1)(ii): The employer did not ensure that no employee uses any anchorage before the employer has obtained written information from the building owner that each anchorage meets the requirements of paragraph (b)(1)(i) of this section. The employer did not keep the information for the duration of the job. Fire Station 1 Hose Tower: A scaffold vertical post was used to anchor a rope decent system for firefighter rescue training. Employees were exposed to fall hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Fire Station 1 Alarm Room: Two radio charging stations that consisted of six charging ports each at three amps per port (thirty-six amps total) were plugged into a relocatable power tap designed for low amperage equipment. Employees were exposed to fire and electrical hazards.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a. Station 1 Galley: The electrical junction box on the southeast wall did not have a cover. Employees were exposed to electrical hazards. b. Station 2 Day room: The electrical junction box under the training computer did not have a cover. Employees were exposed to electrical hazards.
Recent events (1)
- — Z (O) $0
More inspections at U.S. NAVY
JOINT BASE PEARL HBR HICKAM, HI—2024-03-22 00:00:00
U.S. NAVY
JOINT BASE PEARL HBR HICKAM, HI—2023-08-02 00:00:00
U.S. NAVY
KAILUA, HI—2021-04-07 00:00:00
U.S. NAVY
BREMERTON, WA—2007-12-07 00:00:00
U.S. NAVY
PORT HADLOCK, WA—2004-04-26 00:00:00
U.S. NAVY
View U.S. NAVY's full OSHA safety record →
More inspections in this industry (NAICS 928110)
FORT LEE, VA—2026-07-15
U.S. DEPARTMENT OF THE ARMY - FORT LEE
COLUMBIA, SC—2026-07-02
U.S. DEPARTMENT OF VETERANS AFFAIRS
COLUMBIA, SC—2026-07-02
U.S. DEPT OF ARMY
COLUMBIA, SC—2026-07-02
U.S. DEPT OF ARMY
EL PASO, TX—2026-06-24
U.S. CUSTOMS AND BORDER PROTECTION
More inspections in HI
LAHAINA, HI—2026-07-15
PALI KOA LLC
HONOLULU, HI—2026-07-14
KAIKAI WANG
KAILUA, HI—2026-07-08
HELEMAI LAWN & GARDEN
MAKAWAO, HI—2026-07-01
HALIIMAILE PINEAPPLE COMPANY LTD
HONOLULU, HI—2026-06-29
GP ENERGY COMPANY LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346887318.