Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: TENNESSEE VALLEY AUTHORITY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of TENNESSEE VALLEY AUTHORITY in 615 ELM TREE ROAD, BROWNSVILLE, TN 38012 (NAICS 221112). OSHA activity number 346957210.

Watch Tennessee Valley Authority — free Get an email when a new federal OSHA severe-injury report for Tennessee Valley Authority is published. One employer, no account, unsubscribe in one click.
Site address
615 ELM TREE ROAD
City
BROWNSVILLE
State
TN
ZIP
38012
Mailing
1101 MARKET STREET MAIL STOP BR5C, CHATTANOOGA, TN 37402
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
11
Ownership type
D

3 citations on file for this inspection.

1910.269 C02

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(c)(2):  The job briefing did not cover at least the following subjects:  hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements:  a) On or about September 1, 2023 at the Lagoon Creek Combustion Turbine employees performing fuel gas supply energy isolation were exposed to fire and struck-by hazards and the employer did not ensure the job briefing covered all the hazards associated with the job, and work procedures involved.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D02 IV B

Deleted Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(d)(2)(iv)(B): The procedure did not clearly and specifically outline the procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:  a) On or about September 1, 2023 at the Lagoon Creek Combustion Turbine employees performing fuel gas supply energy isolation were exposed to fire and struck-by hazards and the employer did not ensure the procedure clearly and specifically outline the procedural steps for shutting down equipment to control hazardous energy.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D06 II

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(d)(6)(ii):  The machine or equipment was not turned off or shut down using the procedures established for the machine or equipment.  An orderly shutdown was not used to avoid any additional or increased hazards to employees as a result of the equipment stoppage:  a) On or about September 1, 2023 at the Lagoon Creek Combustion Turbine employees performing fuel gas supply energy isolation utilized procedures that did not avoid any additional or increased hazards to employees as a result of the equipment stoppage in that ignition sources were not eliminated or controlled and struck-by hazards were created through the venting of high pressure natural gas without decreasing the pressure as much as possible prior to opening of the vent pipes.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View TENNESSEE VALLEY AUTHORITY's full OSHA safety record →