Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ROBERT E BUSH NAVAL HOSPITAL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ROBERT E BUSH NAVAL HOSPITAL in 1145 STURGIS ROAD, TWENTYNINE PALMS MCB, CA 92278 (NAICS 622110). OSHA activity number 347028557.

Watch Robert E Bush Naval Hospital — free Get an email when a new federal OSHA severe-injury report for Robert E Bush Naval Hospital is published. One employer, no account, unsubscribe in one click.
Site address
1145 STURGIS ROAD
City
TWENTYNINE PALMS MCB
State
CA
ZIP
92278
Mailing
1145 STURGIS ROAD, TWENTYNINE PALMS MCB, CA 92278
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
92
Ownership type
D

6 citations on file for this inspection.

1910.23 B10

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(b)(10): The employer did not ensure that any ladder with structural or other defects as immediately tagged "Dangerous: Do Not Use" or with similar language in accordance with � 1910.145 and removed from service until repaired in accordance with � 1910.22(d), or replaced.  C105, Electrical Room: On and or before October 11, 2023, maintenance employee(s) used ladders with worn and illegible maximum load rating labels. The employer did not immediately tag defective ladders with "Dangerous: Do Not Use" or with other similar language. Employee(s) were exposed to ladder overloading, mechanical failure and/or fall hazard(s)
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 G02

Serious Gravity 5 3 instances 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.36(g)(2): An exit access was not at least 28 inches (71.1 cm) wide at all points and the width of the exit and exit discharge was not at least equal to the width of the exit access.  On and or before October 11, 2023, multiple aisles and/or exit access points were not at least 28 inches wide at all points. Employees were potentially exposed to a narrow escape route and fire hazard.  In the following locations: a) Information Management Department, Help Desk Office, H109, (57) Dell PC P2222H monitors were stacked and created a narrow exit approximately 26 inches. b) Lab main room, (2) blue Helmer refrigerators were configured where it created a narrow exit approximately 26 inches.  c) Lab storage room D103, metal shelves were configured where it created a narrow exit approximately 18.5 inches on the right side and 22 inches on the left side.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On and or before October 11, 2023, multiple appliances such as refrigerators and space heaters were plugged into relocatable power taps and/or "daisy chained" in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical shock and/or fire hazards.  In the following locations: a) G210 Breakroom, a White Westinghouse Fridge was plugged into a white unlabeled relocatable power tap.  b) H109, Information Management Department, Help Desk Office, back right-hand corner cubical, a Lakewood Heater was plugged into a Triplite relocatable power tap.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 3 instances 92 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  On and or before October 11, 2023, employee(s) stored ladders, carts, paint, and ceiling tiles in front of the circuit breaker panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).  In the following locations: a) 3rd floor multi ward electrical room b) Room C105 c) Room C120
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 D02

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(d)(2): The employer did not ensure that hazardous conditions on walking-working surfaces are corrected or repaired before an employee uses the walking-working surface again. The employer did not ensure that if the correction or repair cannot be made immediately, the hazard is guarded to prevent employees from using the walking-working surface until the hazard is corrected or repaired.  H106, Information Management Department, Center right hand section of room: On and/or before October 11, 2023, employee(s) used a silver metal shelf to store/retrieve dell computers and keyboards. The employer did not guard the hole in the floor next to the shelf until the hazard was corrected or repaired. Employee(s) were exposed to trip and fall hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E02

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  Operating Room, Main Entrance: On and/or before October 11, 2023, the Ansul Sentry fire extinguisher No. WK-930324 was not visually inspected at least monthly. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ROBERT E BUSH NAVAL HOSPITAL's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347028557.