Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: ERC ICT, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ERC ICT, LLC in 2410 MCJUNKIN ROAD, LAKELAND, FL 33803 (NAICS 325510). OSHA activity number 347218562.

Watch ERC ICT, LLC — free Get an email when a new federal OSHA severe-injury report for ERC ICT, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ERC ICT, LLC
Site address
2410 MCJUNKIN ROAD
City
LAKELAND
State
FL
ZIP
33803
Mailing
2410 MCJUNKIN ROAD, LAKELAND, FL 33803
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325510
Employees
21
Ownership type
A

9 citations on file for this inspection.

1910.25 B03

Other-than-serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2765.00 · Current $1936.00 Reduced
29 CFR 1910.25(b)(3): The employer did not ensure that stairs have uniform riser heights and tread depths between landings.  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to fall injuries, in that the stairs used to access the feed platform for the red high speed disperser mixing machine did not have uniform riser heights.
Recent events (2)
  • — I (O) $1935.5
  • — Z (S) $2765

1910.37 B02

Other-than-serious Gravity 5 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $3687.00 · Current $2581.00 Reduced
29 CFR  1910.37(b)(2):Each exit was not clearly visible and marked by a sign reading "Exit":  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to fire hazards in that a door in the maintenance shop used as an emergency exit to the outside of the building was not marked by a sign reading "Exit".
Recent events (2)
  • — I (O) $2580.9
  • — Z (S) $3687

1910.37 B06

Other-than-serious Gravity 5 3 instances 9 exposed
Issued
Abate by
Penalty
Initial $3687.00 · Current $2581.00 Reduced
29 CFR  1910.37(b)(6):Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to fire hazards in that the employer did not ensure the EXIT sign on top of Warehouse Entrance from and Exit to the Office Area was illuminated.  b) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to fire hazards in that the employer did not ensure the EXIT sign on top of the Side Loading Dock Entrance/Exit was illuminated.  c) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to fire hazards in that the employer did not ensure the EXIT sign on top of the Rear Warehouse Door near Mixer #1 was illuminated.
Recent events (2)
  • — I (O) $2580.9
  • — Z (S) $3687

1910.145 C03

Other-than-serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2765.00 · Current $1936.00 Reduced
29 CFR  1910.145(c)(3):Safety instruction sign(s) were not used where there was a need for general instructions and suggestions relative to safety measure(s):  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to chemical burn hazards in that the safety shower was not labelled with a safety instruction sign for use.
Recent events (2)
  • — I (O) $1935.5
  • — Z (S) $2765

1910.151 C

Serious Gravity 5 4 instances 10 exposed
Issued
Abate by
Penalty
Initial $4610.00 · Current $3227.00 Reduced
29 CFR  1910.151(c):Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to corrosive chemical hazards, in that, the eye wash located on the wall by Mixer #2 and #3 does not provide 15 minutes of continuous flow.  b) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to corrosive chemical hazards, in that, the  eye wash located by Door #4 and Mixer #1 does not provide 15 minutes of continuous flow.  c) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to corrosive chemical hazards, in that, the eye wash located over the sink in the maintenance shop does not provide 15 minutes of continuous flow.  d) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to corrosive chemical hazards, in that, the eye wash located on the outside wall of the lab does not provide 15 minutes of continuous flow.  e) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL: On or about January 18, 2024, the employer exposed employees to chemical burn hazards in that the safety shower was not adequately designed and installed in accordance with ANSI/ISEA Z358.1-2014.
Recent events (2)
  • — I (S) $3227
  • — Z (S) $4610

1910.178 A06

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $3687.00 · Current $2581.00 Reduced
29 CFR  1910.178(a)(6):  The employer did not ensure that all nameplates or markings on a Powered Industrial Truck (PIT) were maintained in a legible condition.  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer failed to maintain the nameplate and markings in a legible condition on a Yale model forklift.
Recent events (2)
  • — I (S) $2580.9
  • — Z (S) $3687

1910.303 G01 II

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3687.00 · Current $2581.00 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground may not be used for storage.   a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to electrical hazards in that electrical panels near the Side Loading Dock Entrance/Exit were blocked.
Recent events (2)
  • — I (O) $2580.9
  • — Z (S) $3687

1910.305 G01 IV A

Other-than-serious Gravity 10 1 instance 11 exposed
Issued
Abate by
Penalty
Initial $6452.00 · Current $4516.00 Reduced
29 CFR  1910.305(g)(1)(iv)(A): The employer exposed employees to electrical and fire hazards in that flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to electrical hazards in that a flexible cord, supplying energy to the "Overhang Storage Area" outside the building was used as a substitute for fixed wiring.
Recent events (2)
  • — I (O) $4516.4
  • — Z (S) $6452

1910.305 G01 IV C

Other-than-serious Gravity 5 1 instance 11 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(C): The employer exposed employees to electrical and fire hazards in that flexible cords and/or cables were run through a window to energize an outdoor storage area which is not specifically permitted otherwise in paragraph (g)(1)(ii) of this section.  a) At ERC ICT, LLC dba Innovative Concrete Technology Corp, located at 2410 McJunkin Road, Lakeland, FL:  On or about January 18, 2024, the employer exposed employees to electrical hazards in that a flexible cord, supplying energy to the "Overhang Storage Area" outside the building was run through a window to the outside.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View ERC ICT, LLC's full OSHA safety record →