BRAINTREE, MA —
OSHA Inspection: NORTHEAST SANITATION SERVICES, LLC
Unprogrammed Other inspection · Health discipline
At a glance
On , OSHA opened an unprogrammed Other health inspection of NORTHEAST SANITATION SERVICES, LLC in 200 COMMERCE DRIVE, BRAINTREE, MA 02184 (NAICS 561720). OSHA activity number 347288565.
Where did this inspection happen?
- Establishment
- NORTHEAST SANITATION SERVICES, LLC
- Site address
- 200 COMMERCE DRIVE
- City
- BRAINTREE
- State
- MA
- ZIP
- 02184
- Mailing
- 239 RISING SUN AVENUE, ATCO, NJ 08004
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561720
- Employees
- 15
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.147 C04 II B
- Issued
- Abate by
- Penalty
- Initial $4610.00 · Current $2250.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedures did not clearly and specifically outline the steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy. Location: Spiral Freezers in Value Added Room Instance A: The company's written LOTO procedures, as detailed in its SSOP for spiral freezers, allows for servicing of freezer conveyors without the conveyors being locked out. Instance B: The company's written LOTO procedures do not address the Freezer lighting which remains energized during cleaning and sanitation tasks. Instance C: The company's written procedures are in English while the bulk of its employees utilizing those procedures are not fluent in English.
Recent events (2)
- — I (S) $2250
- — Z (S) $4610
1910.147 C04 II C
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(C): The energy control procedure did not clearly and specifically outline the steps for placement, removal and transfer of lockout devices or tagout devices and the responsibility for them. Location: Spiral Freezers in Value Added Room The company's written LOTO procedures do not address the coordination of the application and removal of LOTO devices between supervisory and non-supervisory employees.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C04 II D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(D):The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures. Location: Spiral Freezers in Value Added Room The company's LOTO procedures do not specify how verification of de-energization should occur.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(6)(i):The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: Location: spiral freezers in Value Added Room The company had not performed inspections to ensure that employees were following LOTO procedures.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 F02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(f)(2)(i):When outside servicing personnel were engaged in activities in a facility, the onsite employer and the outside employer did not inform each other of their respective lockout or tagout procedures: Location: Spiral Freezers in Value Added Room The company had not exchanged LOTO procedures information with the host employer and company employees did not know whether and how the refrigeration system was 'turned off'.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 H01
- Issued
- Abate by
- Penalty
- Initial $4610.00 · Current $2250.00 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1):Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: Location: Channel Fish Processing Braintree facility Employees were not adequately trained on the hazard posed by the carbon dioxide refrigerant.
Recent events (2)
- — I (S) $2250
- — Z (S) $4610
More inspections in this industry (NAICS 561720)
PALM BAY, FL—2026-07-10 00:00:00
ASCEND BUILDING SERVICES, LLC
NOLENSVILLE, TN—2026-07-08 00:00:00
BUSY BS RESIDENTIAL CLEANING COMPANY
TACOMA, WA—2026-07-07 00:00:00
WA317991946 - COASTAL BUSINESS SERVICES GROUP INC
POULSBO, WA—2026-07-07 00:00:00
WA317991849 - SIMPLY HOUSE CLEANING LLC
DIXON, CA—2026-07-07 00:00:00
SANITATION PROCESS CONTROL, LLC
More inspections in MA
BELLINGHAM, MA—2026-07-16 00:00:00
BELLINGHAM DEPARTMENT OF PUBLIC WORKS
PLYMOUTH, MA—2026-07-15 00:00:00
TECH-ETCH, INC.
WESTFIELD, MA—2026-07-15 00:00:00
BOISE CASCADE BUILDING MATERIALS DISTRIBUTION, L.L.C.
QUINCY, MA—2026-07-15 00:00:00
UNITEDWOR VM CONTRACTOR CORP
FALL RIVER, MA—2026-07-15 00:00:00
CRESCO LABS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347288565.