Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EVERGREEN RECYCLING, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of EVERGREEN RECYCLING, LLC in 136C FULLER RD, ALBANY, NY 12205 (NAICS 423930). OSHA activity number 348131418.

Watch Evergreen Recycling, LLC — free Get an email when a new federal OSHA severe-injury report for Evergreen Recycling, LLC is published. One employer, no account, unsubscribe in one click.
Site address
136C FULLER RD
City
ALBANY
State
NY
ZIP
12205
Mailing
136C FULLER RD, ALBANY, NY 12205
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Last modified
Data loaded
NAICS code
423930
Employees
80
Ownership type
A

3 citations on file for this inspection.

1910.305 B01 II

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $11823.00 · Current $7685.00 Reduced
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   a) Plant floor outside high voltage cage 1: On March 25, 2025, For employees resetting a tripped breaker at panel with exposed busbar, employees were exposed to electric shock due to knockouts/cover plate being open in a 120/240v breaker box.
Recent events (2)
  • — I (O) $7684.95
  • — Z (S) $11823

1910.305 E01

Serious Gravity 10 1 instance 80 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $10758.00 Reduced
29 CFR  1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a) Multiple locations on the plant floor: On or about March 25, 2025, employees working on or around the electrical panels and breaker box's located in wet and damp environments, were exposed to electric shock.  The employer did not provide means to prevent water and/or moisture from accumulating in or around the electrical panels and breaker box's.
Recent events (2)
  • — I (S) $10757.5
  • — Z (S) $16550

1910.303 G01 II

Other-than-serious 3 instances 80 exposed
Issued
Abate by
Penalty
Initial $1328.00 · Current $863.00 Reduced
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage:  a) Plant floor outside high voltage cage 1: On March 25, 2025, the main electrical panels for wash line 1 located on the plant floor, were blocked by a Jersey barrier and metal pipes stored within 17-20 inches from the panels, obstructing access to the electric panel if access is needed for emergency, or maintenance activity.    b)  Plant floor outside high voltage cage  2 - On March 25, 2025, the main control panels for wash line 2 located on the plant floor, were blocked by a Jersey barrier stored within approximately 24 inches  from the panels, obstructing access to the electric panel if access is needed for emergency, or maintenance activity.   c) Plant floor outside high voltage cage wash lines - On March 25, 2025, the main control panels for wash line 1 & 2 located on the plant floor, were blocked by plastic bins filled with shredded plastic flakes approximately 24 inches from the panels, obstructing access to the electric panel if access is needed for emergency, or maintenance activity.