ARCADIA, CA —
OSHA Inspection: DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST in 701 N SANTA ANITA AVENUE, ARCADIA, CA 91006 (NAICS 115310). OSHA activity number 348736661.
Where did this inspection happen?
- Establishment
- DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
- Site address
- 701 N SANTA ANITA AVENUE
- City
- ARCADIA
- State
- CA
- ZIP
- 91006
- Mailing
- 701 N SANTA ANITA AVENUE, ARCADIA, CA 91006
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 115310
- Employees
- 80
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.37 A04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: HQ, 1st floor, Public service section: On or about February 9, 2026, and at times prior thereto, approximately 13ceiling tiles were missing throughout the work area. This condition would delay the activation of the sprinkler system(s) preventing a proper barrier and restricting the movement of smoke in accordance with NFPA 101 8.5.1. Employee(s) were potentially exposed to fire and smoke hazard(s).
Recent events (1)
- — Z (S) $0
1910.106 D03 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.106(d)(3)(ii): Storage cabinet(s) for flammable liquids were not designed or constructed to meet minimal fire resistance as required: Warehouse D: On or about February 9, 2026, and at times prior thereto, flammable liquids such as CHEMSEARCH NATURALIZER Orange Oil Degreaser was stored in a silver cabinet which was not designed or constructed to meet minimal fire resistance requirements. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.159 C02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.159(c)(2): The employer shall properly maintain an automatic sprinkler system installed to comply with this section. The employer shall assure that a main drain flow test is performed on each system annually. The inspector's test valve shall be opened at least every two years to assure that the sprinkler system operates properly. On or about February 09, 2026, and at times prior thereto, the employer did not properly maintain or inspect the installed automatic sprinkler system. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) HQ building b) ATCC building
Recent events (1)
- — Z (S) $0
1910.165 D01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.165(d)(1): Employee alarm systems were not maintained in operating condition: On or about February 9, 2026, and at times prior thereto, the Hochiki FireNet Plus alarm systems were not maintained in an operating condition. This condition potentially exposed employee(s) to fire hazard(s). In the following location(s): a) HQ building b) ATCC building
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: HQ building, West end staircase: On or about February 09, 2026, and times prior thereto, a flexible cord which was providing power to a DMP Alarm Communicator was run through a hole in the wall. This condition potentially exposed employee(s) to electrical hazard(s).
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: On or about February 9, 2026, and at times prior thereto, fire extinguisher(s) mounted/staged were not up to date with their annual maintenance check. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) HQ building b) Radio office building Notice 1, Item 1, 29 CFR 1910.157(e)(3) as required by 29 CFR 1960.8(b): Portable fire extinguishers were not subjected to an annual maintenance check. The employer was cited for a violation of the same standard on July 28th, 2025, Inspection 1827381, August 21, 2025, of final order/settlement, and means of abatement.
Recent events (1)
- — Z (R) $0
1904.32 A04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1904.32(a)(4): The employer did not post an OSHA 300A Form or equivalent by February 1 thru April 30. HQ building: On or about February 9, 2026, and at times prior thereto, the employer did not post an OSHA 300a for calendar year 2025 by February 1.
Recent events (1)
- — Z (O) $0
1910.1200 G08
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s). Warehouse D, Radio Office Building: On or about February 9, 2026, and at times prior thereto, the employer did not have copies of the safety data sheets for each hazardous chemical to include WD-40 and did not ensure that safety data sheets were readily accessible at the worksite. This condition potentially exposed employee(s) to chemical hazard(s).
Recent events (1)
- — Z (O) $0
More inspections at DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
GLENDORA, CA—2026-02-12
DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
SAN FERNANDO, CA—2026-02-11
DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
SAN FERNANDO, CA—2026-02-11
DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
SAN FERNANDO, CA—2026-02-11
DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
ACTON, CA—2026-02-10
DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST
View DEPT. OF AGRICULTURE ? FS ? ANGELES NATIONAL FOREST's full OSHA safety record →
More inspections in this industry (NAICS 115310)
WASHINGTON, DC—2026-06-30
U.S. DEPARTMENT OF AGRICULTURE
MARIENVILLE, PA—2026-06-30
UNITED STATES FOREST SERVICE
DIANA, TX—2026-06-26
AMIGO FORESTRY SERVICE, INC
RYDERWOOD, WA—2026-06-09
WA317991576 - C & V REFORESTATION INC
OROVILLE, CA—2026-05-26
ALPINE LAND INFORMATION SERVICES, INC.
More inspections in CA
IRVINE, CA—2026-07-13
SNEARY CONSTRUCTION, INC.
IRVINE, CA—2026-07-13
KUKBO DESIGN USA LLC
ENCINITAS, CA—2026-07-13
LOU RIDDLE CONSTRUCTION
CANYON COUNTRY, CA—2026-07-13
COLLEGE OF THE CANYONS
LINDSAY, CA—2026-07-13
NATIONAL DIVERSIFIED SALES, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348736661.