104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14194328

VOLTAGE BACKFEED,ELECTRICAL,E PTD,ELEC UTILITY WORK,ELECTRIC SHOCK,UNDRGRD POWER LINE

Event
VOLTAGE BACKFEED,ELECTRICAL,E PTD,ELEC UTILITY WORK,ELECTRIC SHOCK,UNDRGRD POWER LINE
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14194328
Report ID
352440

Event description

ELECTRIC SHOCK - CONTACT WITH UNDERGROUND LINE

Investigation abstract

AN EMPLOYEE WAS TO SPLICE A 13-KILOVOLT UNDERGROUND POWER CABLE IN A PIT THAT WA EMPLOYEE WAS WORKING. WHEN THE EMPLOYEE CONTACTED THE CABLE, HE RECEIVED AN ELEC TRIC SHOCK FOR WHICH HE WAS HOSPITALIZED. HE HAD NOT TESTED THE CABLE BEFORE HE STARTED WORK. S 3 FEET DEEP, 54 INCHES WIDE, AND 5 FEET LONG. THE CABLE WAS PRESUMED TO BE DEE NERGIZED AS IT HAD NOT BEEN CONNECTED TO ITS POWER SOURCE. HOWEVER, THE OTHER EN D OF THE CABLE WAS CONNECTED TO A TRANSFORMER AT THE REAR OF A FAST-FOOD RESTAUR ANT THAT WAS UNDER CONSTRUCTION ABOUT 60 FEET FROM THE PIT. THE SECONDARY OF THE TRANSFORMER WAS CONNECTED TO A PANELBOARD AT THE RESTAURANT. AN ELECTRICIAN INS TALLING THE ELECTRICAL SERVICE IN THE RESTAURANT HAD CONNECTED A FLEXIBLE CORD F ROM THE 240-VOLT TEMPORARY SERVICE AT THE SITE TO THE PANELBOARD. CURRENT FROM T HE TEMPORARY SERVICE BACKFED THE TRANSFORMER, ENERGIZING THE CABLE ON WHICH THE

Victim

  1. #1 Hospitalized Age 39 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    18
    Environmental factor
    8
    Task assigned