Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14198626

EASTON UTILITIES COMMISSION ELECTRIC DEPARTMENT

Event
BURN, CLOTHING, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT
NAICS
000000
Inspection type
Accident-driven
Activity number
#18820035
Employer profile
EASTON UTILITIES COMMISSION ELECTRIC DEPARTMENT
Summary number
14198626
Report ID
352410

Event description

ELECTRIC SHOCK AND BURN - DIRECT CONTACT WITH OVERHEAD LINE

Investigation abstract

A LINEMAN IN THE BUCKET OF AN AERIAL LIFT WAS INSTALLING DEENERGIZED EQUIPMENT O INE HOSE, AND THE LINEMAN WAS NOT WEARING RUBBER INSULATED GLOVES OR SLEEVES. N THE CROSSARM OF A 30-FOOT-HIGH WOOD POLE. THE POLE WAS NEAR 3 BARE OVERHEAD PO WER LINES, EACH ENERGIZED AT 4900 VOLTS, PHASE TO GROUND. WHILE ATTACHING A 3-FO OT, BARE, 6 AWG COPPER BONDNG JUMPER TO A LINE DISCONNECT WITH A JUMPER IN HIS B ARE HAND, THE EMPLOYEE REACHED ACROSS THE CROSSARM FROM NORTH TO SOUTH AND CONTA CTED THE WESTERN-MOST ENERGIZED CONDUCTOR. THE LINEMAN'S CHEST CONTACTED A BARE LIGHTNING ARRESTER, AND HE RECEIVED AN ELECTRIC SHOCK AND BURNS TO HIS HANDS AND CHEST. EACH OF THE 3 CONDUCTORS WERE COVERED WITH 6-FOOT LENGTHS OF RUBBER LINE HOSE AT THE SOUTH SIDE OF THE CROSSARM. HOWEVER, THE NORTH SIDE HAD NO RUBBER L

Victim

  1. #1 Hospitalized Age 58 M

    Nature of injury
    10
    Part of body
    12
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    20
    Environmental factor
    18
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.