105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14234454

E GI IV,ELECTRICAL,ELECTRIC SWITCH,ELECTROCUTED,ELECTRICAL WORK,LOCKOUT

Event
E GI IV,ELECTRICAL,ELECTRIC SWITCH,ELECTROCUTED,ELECTRICAL WORK,LOCKOUT
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14234454
Report ID
627700

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

AN EMPLOYEE WAS INSTALLING AN ELECTRIC MOTOR IN A TEXTURE MACHINE AT A BRICK MAN UFACTURING PLANT. THE DISCONNECTING MEANS FOR THE MOTOR WAS NOT DEENERGIZED AT T HE TIME. A SECOND EMPLOYEE, WHO WAS ASSISTING IN THE INSTALLATION, STATED THAT T HEY CHECKED THE SWITCH BOX FROM A DISTANCE BEFORE STARTING WORK AND THAT THE SWI TCH APPEARED TO BE IN THE OPEN POSITION. THE SWITCH (WESTINGHOUSE SERIAL NUMBER C46-351) WAS SPRING LOADED AND WAS NOT IN THE FULL OPEN POSITION. THE FIRST EMPL OYEE WAS ELECTROCUTED WHEN HE CONTACTED ENERGIZED PARTS.

Victim

  1. #1 Fatality Age 57 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    13
    Environmental factor
    18
    Hazardous substance
    8870
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.