OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,E PTD,ELEC UTILITY WORK,ELECTRIC SHOCK,TRANSFORMER

Event
OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,E PTD,ELEC UTILITY WORK,ELECTRIC SHOCK,TRANSFORMER
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14235667
Report ID
552700

Event description

ELECTRIC SHOCK - CONTACT WITH ENERGIZED TRANSFORMER CASE

Investigation abstract

A PROJECT WAS UNDERTAKEN TO MOVE OVERHEAD POWER LINES FROM AN OLD SET OF POLES T O A NEW SET THAT HAD ALREADY BEEN INSTALLED. STANDING IN AN AERIAL LIFT, AN EMPL OYEE WAS WORKING ON THE POWER LINES. THE EMPLOYEE MADE SIMULTANEOUS CONTACT WITH THE UNGROUNDED CASE OF A TRANSFORMER AND A SECONDARY LINE, AND HE RECEIVED AN E LECTRIC SHOCK. THE TRANSFORMER, WHICH HAD BEEN INSTALLED BY THE EMPLOYEE EARLIER IN THE WEEK, HAD 4160 VOLTS FROM THE PRIMARY IMPRESSED ON ITS CASE.

Victim

  1. #1 Hospitalized Age 38 M

    Nature of injury
    10
    Part of body
    13
    Event type
    13
    Source
    5
    Occupation code
    577
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1