104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14237630

ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,LOCKOUT,E PTD,ELEC UTILITY WORK,TRANSFORMER,UTILITY POLE

Event
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,LOCKOUT,E PTD,ELEC UTILITY WORK,TRANSFORMER,UTILITY POLE
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14237630
Report ID
627100

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

A power line worker was on a utility pole, connecting a transformer to a 120-vol t secondary and a 7200-volt overhead power line. He apparently thought the 7200- volt primary was deenergized, so he was not wearing rubber insulating gloves. He connected the secondary conductors without trouble. However, another crew had e nergized a second section of overhead line connected to a second transformer tha t also supplied power to the 120-volt secondary. This energized the primary side of the transformer the power line worker was working on. When he touched the pr imary lead on the transformer, he was electrocuted.

Victim

  1. #1 Fatality Age 23 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    11
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.