Event description
ELECTRIC SHOCK - GROUND FAULT IN PANELBOARD
Investigation abstract
A KNITTER WAS WORKING ON THE CREEL FOR AN ORAT KNITTING MACHINE. THE EMPLOYEE'S LEFT HIP CONTACTED A RECEPTACLE OUTLET. HE RECEIVED AN ELECTRIC SHOCK AND WAS KN OCKED TO THE FLOOR, AND HE WAS HOSPITALIZED FOR THIS INJURY. ONE CONDUCTOR OF A FOUR-CONDUCTOR CORD HAD LOOSENED FROM ITS TERMINAL INSIDE THE PANELBOARD FOR THE MACHINE'S 240-VOLT POWER SUPPLY. THE LOOSE CONDUCTOR WAS CONTACTING THE EQUIPME NT GROUNDING CONDUCTOR, ENERGIZING THE METAL CREEL OR THE METAL RECEPTACLE OUTLE T BOX OR BOTH.
Victim
-
#1 Hospitalized Age 38 M
- Nature of injury
- 10
- Part of body
- 2
- Event type
- 13
- Source
- 15
- Occupation code
- 739
- Human factor
- 8
- Environmental factor
- 18
- Hazardous substance
- 8870
- Task assigned
- 1