Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14346530

MONTGOMERY ELEVATOR COMPANY

Event
ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELEVATOR
NAICS
000000
Inspection type
Accident-driven
Activity number
#100381276
Employer profile
MONTGOMERY ELEVATOR COMPANY
Summary number
14346530
Report ID
420600

Event description

ELECTRIC SHOCK - GROUND FAULT IN ELEVATOR CIRCUIT

Investigation abstract

AN EMPLOYEE WAS INSTALLING WIRING FOR AN ELEVATOR CAR. AN ELECTRICAL FAULT OCCUR RED IN ONE OF THE CIRCUITS AT AN OVERHEAD LIGHT INSIDE THE ELEVATOR CAR, ENERGIZ ING THE CAR ITSELF AT 120 VOLTS. IN WIRING THE CIRCUIT AT THE PANELBOARD, THE EM PLOYEE HAD NOT CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR FOR THE ELEVATOR. THE REFORE, THE 10-AMPERE FUSE PROTECTING THE CIRCUIT DID NOT DETECT THE FAULT, AND THE CAR REMAINED ENERGIZED. THE EMPLOYEE REACHED INSIDE THE ELEVATOR SHAFT TO RE TRIEVE A 10-FOOT PIECE OF METAL CONDUIT WITH HIS LEFT HAND, WHILE HIS RIGHT HAND WAS ON THE CAR. THE CONDUIT WAS STANDING VERTICALLY ON THE ELEVATOR PIT FLOOR, PROVIDING A PATH TO GROUND. THE EMPLOYEE WAS ELECTROCUTED.

Victim

  1. #1 Fatality Age 30 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    9
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.