104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14348791

E GI V,ELECTRICAL,ELECTROCUTED,ATTACHMENT PLUG,ELECTRIC CORD

Event
E GI V,ELECTRICAL,ELECTROCUTED,ATTACHMENT PLUG,ELECTRIC CORD
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14348791
Report ID
418300

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PLUG

Investigation abstract

A MAINTENANCE EMPLOYEE WAS REPLACING A HYDRAULIC CYLINDER ON THE BOOM OF A PACK- CYLINDER INTO PLACE. THE MOVEMENTS OF HIS BODY OVER THE CORD CAUSED THE TWIST-L OCK ATTACHMENT PLUG TO BECOME DISCONNECTED. THE ENERGIZED ATTACHMENT PLUG ON THE END OF THE CORD REEL FELL ONTO THE EMPLOYEE'S BODY AND ELECTROCUTED HIM. A-BACK. THIS EQUIPMENT IS HEAVY MACHINERY WITH A GRAPPLE ATTACHMENT ON ITS BOOM, AND IT IS USED TO MOVE LOGS. THE HYDRAULIC CYLINDER WAS BEING HELD IN PLACE WIT H A SMALL ELECTRIC HOIST MOUNTED ON AN OVERHEAD BRIDGE. THE 16-INCH ELECTRIC SUP PLY CORD FOR THE HOIST HAD A CORD CONNECTOR ON ITS END RATHER THAN AN ATTACHMENT PLUG. IT WAS CONNECTED TO A TWIST-LOCK ATTACHMENT PLUG ON THE END OF A SPRING-L OADED CORD REEL THAT WAS 10 FEET ABOVE THE FLOOR AND THAT HAD BEEN WIRED (BY AN ELECTRICIAN) TO A 480-VOLT SUPPLY CIRCUIT. (THE HOIST WAS "NEVER" UNPLUGGED.) TH E EMPLOYEE WAS STRADDLING THE BOOM AND WAS LEANING ON THE BOOM TRYING TO PRY THE

Victim

  1. #1 Fatality Age 30 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    519
    Human factor
    14
    Environmental factor
    18
    Hazardous substance
    8870
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.