105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14379457

ELEC PROTECT EQUIP,PROTECTIVE GROUNDING,ELECTRICAL,ELECTRIC SWITCH,POWER LINE WORKER,ELECTROCUTED,E PTD,CIRCUIT BREAKER,ELEC UTILITY WORK

Event
ELEC PROTECT EQUIP,PROTECTIVE GROUNDING,ELECTRICAL,ELECTRIC SWITCH,POWER LINE WORKER,ELECTROCUTED,E PTD,CIRCUIT BREAKER,ELEC UTILITY WORK
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14379457
Report ID
524500

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

AN EMPLOYEE WAS WORKING FROM AN AERIAL LIFT, GROUNDING THE LINE SIDE OF AN OIL C IRCUIT BREAKER. HE POSITIONED THE BUCKET BETWEEN THE SOUTH PHASE AND THE CENTER PHASE AND HAD ATTACHED ONE END OF THE PROTECTIVE GROUND TO THE STEEL STRUCTURE S ERVING AS GROUND. THE GROUNDING CABLE PASSED BETWEEN THE INSULATOR AND THE BLADE OF A SWITCH. THIS POSITION WOULD HAVE INTERFERED WITH THE REMOVAL OF THE SWITCH . THERE WERE NO WITNESSES TO THE ACCIDENT, BUT IT WAS APPARENT THAT THE EMPLOYEE TRIED TO PASS THE LOOSE END OF THE GROUNDING CABLE AROUND THE BLADE OF THE SWIT CH. IN SO DOING, HE APPARENTLY CONTACTED THE ENERGIZED BLADE OF THE SWITCH AND W AS ELECTROCUTED.

Victim

  1. #1 Fatality Age 45 M

    Nature of injury
    10
    Part of body
    12
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1