Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14380083

GEORGE HAUCK CO.

Event
ELEC INSULATION, ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CORD, ELECTRIC LIGHT--PORT
NAICS
000000
Inspection type
Accident-driven
Activity number
#101373686
Employer profile
GEORGE HAUCK CO.
Summary number
14380083
Report ID
522000

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

TWO EMPLOYEES, A JOURNEYMAN HEATING, VENTILATION, AND AIR CONDITIONING MECHANIC ION CORD SETS, AND THE CABLE WAS UNGROUNDED. IT APPEARED THAT THE MECHANIC'S WET CLOTHES CONTACTED ENERGIZED PARTS OF THE CORD AND PLUG CONNECTION THROUGH A DEF ECT IN THE INSULATION ON THE CONDUCTORS. THE MECHANIC, WHO WAS IN CONTACT WITH T HE GROUNDED METAL DUCTWORK, WAS ELECTROCUTED. AND HIS APPRENTICE, WERE INSTALLING A METAL DUCT IN A CRAWL SPACE UNDER A RESIDE NCE. THE MECHANIC WAS PUTTING A METAL ELBOW INTO THE DUCTWORK WHILE HE WAS KNEEL ING ON A DOUBLE-INSULATED DRILL AND A TROUBLE LIGHT CORD. THE DRILL WAS PLUGGED INTO A RECEPTACLE ON THE TROUBLE LIGHT. THE CORD FOR THE LIGHT WAS, IN TURN, CON NECTED TO AN EXTERIOR RECEPTACLE OUTLET OF AN ADJACENT RESIDENCE THROUGH TWO THR EE-WIRE EXTENSION CORD SETS AND A SECTION OF NONMETALLIC-SHEATHED CABLE. THE COR D PASSED THROUGH A DOORWAY ON ITS WAY TO THE CRAWL SPACE. THE BLADES FOR THE EQU IPMENT GROUNDING CONDUCTOR WERE MISSING FROM THE ATTACHMENT PLUGS OF BOTH EXTENS

Victim

  1. #1 Fatality Age 31 M

    Nature of injury
    10
    Part of body
    12
    Event type
    13
    Source
    15
    Occupation code
    534
    Human factor
    9
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.