105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14384382

RECEPTACLE,ELECTRICAL,E GI VII,ELECTROCUTED,GROUND FAULT,ELEC EQUIPMENT--MISC

Event
RECEPTACLE,ELECTRICAL,E GI VII,ELECTROCUTED,GROUND FAULT,ELEC EQUIPMENT--MISC
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14384382
Report ID
523300

Event description

ELECTRIC SHOCK - DEFECTIVE RECEPTACLE

Investigation abstract

AN EMPLOYEE WAS ADJUSTING A WELDING GUN FOR A WIRE FEED OPERATION. THE WELDER WA S PLUGGED INTO A DEFECTIVE 480/277-VOLT, WALL-MOUNTED RECEPTACLE AT A POSITION 1 80 DEGREES OUT OF PROPER ALIGNMENT. THIS IMPROPER ALIGNMENT CAUSED THE EQUIPMENT GROUNDING CONDUCTOR TO BE CONNECTED TO ONE OF THE LINE CONDUCTORS, ENERGIZING T HE FRAME OF THE WELDER. THE EMPLOYEE WAS ELECTROCUTED.

Victim

  1. #1 Fatality Age 35 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    1
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.