104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14393037

E GI V,ELECTRICAL,ELECTROCUTED,GROUND FAULT,EQUIPMENT GROUNDING,ELEC EQUIPMENT--MISC

Event
E GI V,ELECTRICAL,ELECTROCUTED,GROUND FAULT,EQUIPMENT GROUNDING,ELEC EQUIPMENT--MISC
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14393037
Report ID
625700

Event description

ELECTRIC SHOCK - GROUND FAULT IN UTILIZATION EQUIPMENT

Investigation abstract

AN EMPLOYEE WAS OPERATING AN ULTRAVIOLET LIGHT FROM A SPECIAL TRANSFORMER. THE T RANSFORMER STEPPED THE 120-VOLT SUPPLY VOLTAGE TO 240 VOLTS UNTIL THE LIGHT STRU CK AN ARC; THEN THE VOLTAGE WAS DROPPED BACK TO 120 VOLTS. THE OUTER INSULATION ON THE 120-VOLT CORD WAS BROKEN, AND THE EQUIPMENT GROUNDING CONDUCTOR WAS NOT C ONTINUOUS. THE EMPLOYEE, WHO WAS STANDING ON A WET CONCRETE FLOOR, WAS ELECTROCU TED.

Victim

  1. #1 Fatality Age 21 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    9
    Environmental factor
    13
    Task assigned
    1