105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14402671

ELECTRICAL,E GI VII,ELECTROCUTED,PANELBOARD,LIGHTNING,GROUND FAULT,EQUIPMENT GROUNDING,SYSTEM GROUNDING

Event
ELECTRICAL,E GI VII,ELECTROCUTED,PANELBOARD,LIGHTNING,GROUND FAULT,EQUIPMENT GROUNDING,SYSTEM GROUNDING
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14402671
Report ID
626000

Event description

ELECTRIC SHOCK - GROUND FAULT IN PANELBOARD

Investigation abstract

An electrician was opening a panelboard at a remote oil well salt water pumping station. Lightning had apparently caused the lightning arrester resistor to open and caused one of the circuit conductors to become welded to the grounding cond uctor, which was bonded to the box. The grounding electrode for the panelboard w as a 2.4-meter-long (8-foot-long) ground rod. Thus, the ground fault energized t he panelboard to an unknown voltage without drawing enough current to open the c ircuit. The electrician was unaware of this condition. He was standing on the gr ound, which was wet from a recent rainfall, when he contacted the panelboard. Th e electrician was electrocuted.

Victim

  1. #1 Fatality Age 48 M

    Nature of injury
    10
    Part of body
    4
    Event type
    12
    Source
    15
    Occupation code
    575
    Human factor
    20
    Environmental factor
    17
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.