105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14422315

ELEC PROTECT EQUIP,OVERHEAD POWER LINE,PROTECTIVE GROUNDING,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,LOCKOUT,E PTD,ELEC UTILITY WORK

Event
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,PROTECTIVE GROUNDING,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,LOCKOUT,E PTD,ELEC UTILITY WORK
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14422315
Report ID
729700

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Investigation abstract

Two power line workers arrived at the site of a downed phase conductor of a 7200 -volt overhead power line so that they could repair the line. The phase conducto r had been deenergized, but was not yet grounded. One of the power line workers grabbed the conductor and was electrocuted. It is believed that there was backfi eld of unknown voltage from the transformer banks, which energized the phase con ductor.

Victim

  1. #1 Fatality Age 41 M

    Nature of injury
    10
    Part of body
    4
    Event type
    2
    Source
    15
    Occupation code
    577
    Human factor
    9
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.