OSHA Accident Investigation · Summary #14429435
ELECTRICAL,ELECTROCUTED,ELECTRIC PUMP,E C,GROUND FAULT,EQUIPMENT GROUNDING,WATER
Event description
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC PUMP
Investigation abstract
AN EMPLOYEE WAS STANDING IN A WATER-FILLED DEPRESSION WITH A TURUMI SUBMERSIBLE PUMP (MODEL NUMBER NK-15). THE PUMP HAD ITS EQUIPMENT GROUNDING CONDUCTOR CONNEC TED TO ONE OF THE CIRCUIT CONDUCTORS OF AN EXTENSION CORD SET; THUS, ITS FRAME W AS ENERGIZED. THE CORD SET WAS CONNECTED TO A GENERATOR TRAILER PROVIDING POWER TO THE PUMP. THE EMPLOYEE WAS ELECTROCUTED.
Victim
-
#1 Fatality Age 35 M
- Nature of injury
- 10
- Part of body
- 29
- Event type
- 13
- Source
- 15
- Occupation code
- 999
- Human factor
- 12
- Environmental factor
- 13
- Task assigned
- 1