Event description
ELECTRIC SHOCK - GROUND FAULT IN LIGHTING SYSTEM
Investigation abstract
AN EMPLOYEE WAS REWIRING 277-VOLT, 20-AMPERE DRIVEWAY LIGHTS. A SPLICE IN ONE OF THE CIRCUIT CONDUCTORS WAS NOT ADEQUATELY INSULATED, AND AN EXPOSED PORTION OF THE CONDUCTOR WAS CONTACTING A LIGHT POLE. ADDITIONALLY, THE EMPLOYEE HAD NOT GR OUNDED THE EXPOSED NON-CURRENT-CARRYING METAL PARTS OF THE SYSTEM. AS A LIGHT RA IN WAS FALLING, THE EMPLOYEE, WHO WAS KNEELING ON THE GROUND, TIGHTENED ANCHOR B OLTS AT THE BASE OF THE LIGHT STAND. HIS SUPERVISOR WENT INDOORS AND ENERGIZED T HE LIGHTING SYSTEM. THE EMPLOYEE WAS ELECTROCUTED.