OSHA Accident Investigation · Summary #14485437
ELECTRIC MOTOR,E GI V,ELECTRICAL,ELECTROCUTED,GROUND FAULT,EQUIPMENT GROUNDING
Event description
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC MOTOR
Investigation abstract
AN EMPLOYEE WAS WORKING WITH A 480-VOLT, THREE-PHASE ELECTRIC MOTOR. THE MOTOR H AD NO CONTROLLER. THE EMPLOYEE PLACED ONE OF THE CIRCUIT CONDUCTORS (THE "WHITE WIRE") ON THE MOTOR HOUSING AND CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR (THE "GREEN WIRE") TO THE MOTOR LEADS. THIS ENERGIZED THE MOTOR HOUSING AND THE WORK BENCH. THE EMPLOYEE WAS ELECTROCUTED AS HE PLUGGED IN THE MOTOR.
Victim
-
#1 Fatality Age 63 M
- Nature of injury
- 10
- Part of body
- 4
- Event type
- 12
- Source
- 15
- Occupation code
- 999
- Human factor
- 1
- Environmental factor
- 18
- Task assigned
- 1
Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.