Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14485619

TROJAN INDUSTRIES INC.

Event
BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT
NAICS
000000
Inspection type
Accident-driven
Activity number
#100183763
Employer profile
TROJAN INDUSTRIES INC.
Summary number
14485619
Report ID
213600

Event description

BURN - ELECTRICAL FAULT IN PANELBOARD

Investigation abstract

On February 21, 1986, two maintenance workers were replacing a fuse block panel in a 480-volt, 60-ampere, three-phase panelboard. The panelboard was mounted 6.4 meters above grade. The employees were working on a Lift-A-Loft platform. While they were working, one of them caused a phase-to-ground fault. The fault trippe d a 480-volt, 2000-ampere, three-phase breaker, but not before the ensuing elect ric arc melted a potion of the panelboard and severely burned both employees. Th e employees were hospitalized for their injuries. On April 9, 1986, one of the e mployees died of his injuries, and the other was released from the hospital.

Victims (2)

  1. #1 Fatality Age 47 M

    Nature of injury
    5
    Part of body
    19
    Event type
    1
    Source
    15
    Occupation code
    519
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1
  2. #2 Hospitalized Age 30 M

    Nature of injury
    5
    Part of body
    19
    Event type
    1
    Source
    15
    Occupation code
    519
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1