104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14495964

ELECTRICAL,ELECTRIC SWITCH,E GI VII,ELECTROCUTED,CURRENT LEAKAGE,CORROSION,EQUIPMENT GROUNDING

Event
ELECTRICAL,ELECTRIC SWITCH,E GI VII,ELECTROCUTED,CURRENT LEAKAGE,CORROSION,EQUIPMENT GROUNDING
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14495964
Report ID
627100

Event description

ELECTRIC SHOCK - CORROSION-CAUSED FAULT IN SWITCH

Investigation abstract

A 4-FOOT-BY-8-FOOT ROOM IN A SALT GRINDING BAY HOUSED SWITCHES ALONG ONE WALL. A ENERGIZED THE METAL CABLE TRAY AND THE OTHER THREE SWITCHES. THE EMPLOYEE WAS EL ECTROCUTED AS HE TOUCHED ONE OF THE SMALLER SWITCHES. 5-FOOT SECTION OF METAL CABLE TRAY HAD BEEN MOUNTED THERE; AND, ON TOP OF THE C ABLE TRAY, A MAIN SWITCH HAD BEEN INSTALLED WITH A SHORT METAL NIPPLE. THREE OTH ER SWITCHES WERE ALSO INSTALLED ON TOP OF THE TRAY IN THE SAME MANNER. ALL OF TH E SWITCHES WERE RATED 480 VOLTS, 3 PHASE. BECAUSE OF CORROSION PROBLEMS, THE SWI TCHES WERE SUPPLIED BY CONDUCTORS RUN IN NONMETALLIC CONDUIT. HOWEVER, THE SWITC HES WERE OF THE GENERAL-PURPOSE TYPE, AND CORROSION HAD CAUSED LEAKAGE TO DEVELO P FROM THE CENTER PHASE TO THE SWITCH HANDLE. AN EMPLOYEE MOVED THE HANDLE OF TH E MAIN SWITCH IN THE UP POSITION. BECAUSE THE METAL TRAY WAS NOT GROUNDED, THIS

Victim

  1. #1 Fatality Age 35 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    6
    Environmental factor
    9
    Task assigned
    1