OSHA Accident Investigation · Summary #14517809
DIGGER-DERRICK,OVERHEAD POWER LINE,PROTECTIVE GROUNDING,ELECTRICAL,ELECTROCUTED,E PTD,ELEC UTILITY WORK,UTILITY POLE
Event description
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU UTIL POLE
Investigation abstract
A LINE CREW WAS ASSIGNED TO REPLACE A BROKEN UTILITY POLE. THE OLD POLE HAD BEEN SUPPORTING THREE OVERHEAD POWER LINES THAT WERE ENERGIZED EVEN THOUGH THE CIRCU IT BREAKER FOR THE LINES HAD BEEN PULLED. ONE OF THE EMPLOYEES, WEARING RUBBER I NSULATING GLOVES, WAS GUIDING THE NEW POLE INTO PLACE. AS THE POLE WAS BEING POS ITIONED, IT CONTACTED ONE OF THE OVERHEAD LINES. THE EMPLOYEE WHO HAD BEEN GUIDI NG THE POLE ACCIDENTALLY CONTACTED THE GROUNDED TRUCK AND WAS ELECTROCUTED. THE TRUCK HAD BEEN ENERGIZED THROUGH THE CABLE SUPPORTING THE POLE.
Victim
-
#1 Fatality Age 26 M
- Nature of injury
- 10
- Part of body
- 4
- Event type
- 6
- Source
- 15
- Occupation code
- 577
- Human factor
- 14
- Environmental factor
- 18
- Hazardous substance
- 8870
- Task assigned
- 1
Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.