Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14519581

OUACHITA COCA BOTTLING CO. INC.

Event
E GI V, ELECTRICAL, CORD SET, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, PLUG ADAPTER, ELEC EQUIPMENT--MISC
NAICS
000000
Inspection type
Accident-driven
Activity number
#101082139
Employer profile
OUACHITA COCA BOTTLING CO. INC.
Summary number
14519581
Report ID
625700

Event description

ELECTRIC SHOCK - GROUND FAULT IN VENDING MACHINE

Investigation abstract

An employee of a soft drink bottling company was performing a service call at a municipal golf course pro shop. He was checking a soft drink vending machine tha t was not cooling. The soft drink machine was not grounded because it was connec ted to a receptacle outlet through an extension cord set that did not contain an equipment grounding conductor. (An adapter was being used with the machine's at tachment plug.) The employee pulled on the soft drink machine and, in the proces s, touched a grounded snack machine nearby. A ground fault in the soft drink mac hine had energized it, and the employee was electrocuted.

Victim

  1. #1 Fatality Age 27 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    519
    Human factor
    6
    Environmental factor
    18
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.