Event description

ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU AERIAL LIFT

Investigation abstract

A LINEMAN WAS WORKING FROM AN AERIAL LIFT ON A 69-KILOVOLT OVERHEAD POWER LINE. THE BUCKET INSULATION WAS COMPROMISED BY A DRAIN HOLE CUT THROUGH THE OUTER INSU LATION AND BY A DAMAGED INNER LINER. THE EMPLOYEE WAS WORKING IN THE BUCKET ABOV E THE ENERGIZED LINES IN AN AREA WHICH ALLOWED A 5-FOOT CLEARANCE. A GROUNDMAN E STIMATED THE ACTUAL CLEARANCE BETWEEN THE BUCKET AND THE LINES TO BE 6 INCHES. T HE EMPLOYEE WAS HOLDING THE GROUNDED, DEENERGIZED LINE WHEN THE BUCKET CONTACTED THE ENERGIZED CONDUCTOR BELOW. CURRENT PASSED THROUGH THE BUCKET, THROUGH THE B ODY OF THE LINEMAN, AND OUT THROUGH THE GROUNDED DEENERGIZED LINES.