Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #14527204

MISSISSIPPI POWER & LIGHT COMPANY, SOUTHHAVEN DIST

Event
VOLTAGE BACKFEED, ELEC PROTECT EQUIP, ELECTRICAL, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, TRANSFORMER
NAICS
000000
Inspection type
Accident-driven
Activity number
#100372861
Employer profile
MISSISSIPPI POWER & LIGHT COMPANY, SOUTHHAVEN DIST
Summary number
14527204
Report ID
419400

Event description

ELECTRIC SHOCK - VOLTAGE BACKFEED IN TRANSFORMER

Investigation abstract

AN EMPLOYEE WAS WORKING ON A DEENERGIZED 110-KILOVOLT-AMPERE TRANSFORMER. THE TR ANSFORMER WAS SUPPLIED WITH 240 VOLTS TO POWER THE TAP CHANGER, AND THE VOLTAGE FED BACK THROUGH THE TRANSFORMER. THE EMPLOYEE WAS CONNECTING A METER TO THE HIG H AND LOW VOLTAGE SIDES OF THE TRANSFORMER WHEN HE MADE CONTACT WITH THE NEUTRAL AND PHASE CONDUCTORS, RESULTING IN HIS ELECTROCUTION.

Victim

  1. #1 Fatality Age 37 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.