OSHA Accident Investigation · Summary #14530018
E GI IV,ELECTRICAL,ELECTROCUTED,ELECTRICAL WORK,LOCKOUT
Event description
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS
Investigation abstract
AN EMPLOYEE WAS UPGRADING A BRANCH CIRCUIT BY REPLACING #10 AWG CONDUCTORS WITH #8 AWG CONDUCTORS TO ACCOMMODATE EQUIPMENT THAT DREW MORE CURRENT. AN INADEQUATE LOCKOUT AND TAGGING PROCEDURE (INADEQUATE PROVISIONS FOR ENSURING THE DEENERGIZ ED CONDITION OF CONDUCTORS) LED TO AN EMPLOYEE'S CONTACTING LIVE PARTS ENERGIZED AT 277 VOLTS TO GROUND (480 VOLTS PHASE TO PHASE). THE EMPLOYEE WAS ELECTROCUTE D.
Victim
-
#1 Fatality Age 24 M
- Nature of injury
- 10
- Part of body
- 4
- Event type
- 13
- Source
- 15
- Occupation code
- 575
- Human factor
- 13
- Environmental factor
- 18
- Task assigned
- 1
Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.