104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14541809

LIGHTING CIRCUIT,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,ELECTRICAL WORK,LOCKOUT,E C,TAG,ELECTRICAL BOX

Event
LIGHTING CIRCUIT,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,ELECTRICAL WORK,LOCKOUT,E C,TAG,ELECTRICAL BOX
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14541809
Report ID
418100

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH LIVE PARTS

Investigation abstract

AN ELECTRICIAN HAD REMOVED A TEMPORARY LIGHTING FIXTURE IN AN OCCUPIED OFFICE AN D WAS INSTALLING A JUNCTION BOX FOR A PERMANENT FIXTURE. NO LOCKOUT OR TAGGING P ROCEDURE WAS BEING USED. HE WAS DEPENDING ON THE WALL SWITCH TO ISOLATE THE CIRC UIT. BETWEEN THE TIME THE TEMPORARY FIXTURE WAS REMOVED AND THE TIME HE STARTED TO WIRE THE BOX, THE WALL SWITCH HAD BEEN TURNED "ON", ENERGIZING THE CIRCUIT. A PPARENTLY, HE HELD HE BOX IN ONE HAND AND THE CONDUCTOR IN THE OTHER AS HE INSER TED THE CONDUCTOR INTO THE BOX. BURN MARKS INDICATED THAT CURRENT FROM THE 277-V OLT CIRCUIT FLOWED FROM HAND TO HAND. HE WAS ELECTROCUTED.

Victim

  1. #1 Fatality Age 34 M

    Nature of injury
    10
    Part of body
    31
    Event type
    13
    Source
    15
    Occupation code
    575
    Human factor
    13
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.