OSHA Accident Investigation · Summary #14541924
ELECTRICAL,CORD SET,ELECTROCUTED,E C,GROUND FAULT,TEMPORARY WIRING,ELEC EQUIPMENT--MISC
Event description
ELECTRIC SHOCK - GROUND FAULT IN TEMPORARY WIRING
Investigation abstract
AN ELECTRICIAN'S APPRENTICE WAS USING A PORTABLE ELECTRIC HEAT GUN TO CONNECT OV ERHEAD CONDUIT ON A SINGLE-STORY, MULTI-FAMILY BUILDING. WHILE USING THE HEAT GU N, THE EMPLOYEE WAS ELECTROCUTED BY A GROUND FAULT SOMEWHERE IN THE TEMPORARY WI RING. THE PORTABLE HEAT GUN WAS FOUND TO BE IN PROPER WORKING ORDER; HOWEVER, TH E EXTENSION CORD IN USE WAS OF NON-METALLIC SHEATHED CABLE CONSTRUCTION. ADDITIO NALLY, THE COVER WAS OFF THE TEMPORARY SERVICE PANEL, AND THE SERVICE ENTRANCE C ABLE WAS WIRED INCORRECTLY. THERE WAS NO GROUND-FAULT CIRCUIT INTERRUPTER PROTEC TING THE TEMPORARY RECEPTACLE OUTLET.